ADV200-HC Manual
Page 50 of 55
PROCEDURE for unknown conversion ratio
Set Define axis length
parameter = Init, “Define axis
length” parameter goes to
“Move to limit switch” state.
Move hook until limit switch
trips.
If for any reason you cannot
make the limit switch trip,
move the trolley (or beam) as
far as possible and bring the
“H&C SERVICE \ Define
length” parameter (IPA
11146) to Measure 1.
Measure (A) and make a note
of the distance between the
hook and the ground.
Raise the hook by about 1
meter.
Measure (B) and enter the
shift (Measure 1= B - A) in the
“H&C SERVICE \Measure 1”
parameter (IPA 11192).
This operation lets you
determine the ratio between
motor rpms and actual shift
on the rope.
The “Define axis length”
parameter goes to “Known
position”.
A
B
A
B