7.5.6
Checking the fault monitoring
1.
Disconnect the incoming feeder of the compressor driving motor from the
mains supply for checking the safety devices (e.g. remove LV/HBC fuse
links).
2.
Apply voltage to the control.
3.
Check limit values.
Limit value = see parameter list
4.
Set the motor current limitation acc. to nominal motor data. See parameter
list!
7.5.7
Setting the oil differential pressure
The correct oil pressure must be set in the “Parameters” menu of the control
before the compressor drive motor and thus the heat pump may be started.
Setting value = see parameter list
Warning!
Maintaining the correct oil differential pressure!
► The oil differential pressure being set too high or too low may result in
serious compressor damage or even total breakdown of the compressor af-
ter even a short period of operation!
► The parameter list is part of the product documentation.
Start-up
First start - Start-up procedure
L_151511_2
82
19.12.2019