3.1.1
Technical specifications
Notice
The
GEA RedGenium
is manufactured and delivered according to technical
specifications.
► Optional equipment variants can be considered on the basis of the stand-
ard equipment.
Standard equipment
Designation
Design
Operating pressure:
39 bar(a)
Intended environment:
Closed machine rooms
Ambient temperatures:
+15 °C to +40 °C
Installation altitude:
≤ 1000 m above sea level
Outlet temperature of secondary refriger-
ant
1
:
RedGenium 500 and RedGenium 1100: 3 °C to 35 °C
RedGenium 800: 8 °C to 22 °C
Heat carrier outlet temperature
2
:
+50 °C to +70 °C
Electric motor:
scope of delivery
Refrigerant:
R717
Type of oil:
highly refined mineral oils CPI CP-1009-100
Caution!
Please contact the manufacturer in case of other types of oil.
► Contact the service or the design department of GEA Refrigeration Germany
GmbH.
Oil cooling:
Standard scope of delivery (air cooled)
Oil heaer:
scope of delivery
Oil filter:
Single stage filter
Spare oil filter:
Oil pressure filter cartridge, delivered separately (included)
Oil level switch:
none
Pressure sensors:
on sensor block compressor
Safety pressure switch:
electronic
Overflow valve
scope of delivery
Safety valve HP / LP:
Double safety valve with change-over valve
Flow monitor:
mechanical (paddle)
Control:
GEA Omni™
Communication:
Modbus TCP
Power current and frequency inverter:
Default scope of delivery, cable entry from below
Colour:
RAL 5014 (dove blue), control cabinet RAL 7035
Soundproof housing:
none
Vibration isolators:
without (standard)
Approval of pressure equipment:
CE-PED, Module H (piping)
Documentation:
electronic (provided on a server)
1
temperature difference secondary refrigerant maximum 10 K
2
Heat carrier temperature difference maximum 40 K, higher outlet temperatures on request
Description
Design
L_151511_2
28
19.12.2019