12.4
Dismantling, disposal
Preparatory measures
Notice
Components removed must be disposed of correctly and according to legal
requirements.
► Components may be under excess pressure and must be depressurised
before opening.
► During decommissioning and disposal, it must be ensured that the vari-
ous materials are separated and passed on to the recycling system for fur-
ther processing.
► Disposal of component residues and components as domestic waste is
prohibited.
► In general, the legal regulations for the disposal of electrical equipment
applicable at the installation location must be considered.
► The information in Chapter "Decommissioning" must be observed.
•
Removal and disposal of the product must be carried out in such a way that:
–
the system is free of voltage and is protected against unintentional reacti-
vation,
–
accidents to persons are prevented,
–
material damage is prevented,
–
uncontrolled escape of refrigerant or oil is prevented.
•
Disposal and decommissioning work must only be carried out by personnel
which is qualified according to EN 13313.
•
In case of contact with refrigerant or operating media, their hazardous proper-
ties (e. g. toxicity, inflammability) must be taken into account (see also the
safety data sheet for the refrigerant). Personal protective equipment accord-
ing to EN 378-3 must be worn.
•
National regulations (e. g. EN 378-4, Section 6) must be observed for the
recovery and disposal of refrigerants.
•
National regulations (e. g. EN 378-4, Annex A) must be observed for the
recovery and disposal of operating media (oil).
•
No unauthorised persons must be within the installation area of the plant dur-
ing decommissioning, as they could come into contact with refrigerant.
•
All components of the plant which are not to be re-used, as well as refrigerant
and operating media, must be stored in suitable separate containers. They
must be treated as waste and disposed of safely.
Notice
Re-use of operating media is not possible!
► Operating media must be treated as waste and disposed of safely.
Decommissioning