Chapter 4. Inserting T17 Transducers into the Pipe
68
Model T17 Installation Guide
4.2.3 Aligning the Downstream Transducer (cont.)
8.
Place the alignment fixture over the two studs in the flange at the top of the barrel assembly, and rotate the
barrel flange until the bubble aligns between the tick marks on the vial (see
below). Slowly press the
flange toward the insertion mechanism flange until the gasket and raised faces of both flanges are mated. The
studs should also engage the holes in the insertion mechanism flange. If necessary, the barrel flange can be
rotated slightly to maintain the bubble alignment on the gauge.
Figure 79: Aligning the Barrel Assembly
9.
Remove the fixture and install the remaining studs, washers, and nuts. Tighten them to the correct torque.
10.
Place a tag on the isolation valve stating the following:
DO NOT OPERATE (CLOSE) WHEN
TRANSDUCER IS INSERTED INTO PIPE.
11.
Refer to the flow meter
Startup Guide
to make the transducer electrical connections.
Extended Range Downstream
Transducer Alignment Tool
Placed Over 2 Nozzle/Valve Studs
Nozzle Mark to be Centered Between
2 Bolt Holes On Alignment Fixture
(Significant on Downstream Nozzle Only)
Содержание T17
Страница 1: ...GE Oil Gas Flow 916 128 Rev D September 2020 Model T17 Ultrasonic Flow Transducer Installation Guide ...
Страница 2: ......
Страница 4: ...ii no content intended for this page ...
Страница 62: ...Chapter 2 Installing the Pipe Nozzles 54 Model T17 Installation Guide no content intended for this page ...
Страница 64: ...Chapter 3 Installing an Isolation Valve 56 Model T17 Installation Guide no content intended for this page ...
Страница 88: ...Chapter 6 Specifications 80 Model T17 Installation Guide no content intended for this page ...
Страница 90: ...Warranty 82 Model T17 Installation Guide no content intended for this page ...
Страница 92: ......
Страница 93: ......