Chapter 2. Installing the Pipe Nozzles
18
Model T17 Installation Guide
2.3
Nozzle Installation - MR1 Mid-Radius Path
A
non-diametrical signal path
is one in which the ultrasonic signal between the two transducers does not travel along a
diameter of the pipe. For a
mid-radius
installation, the signal path is offset from the pipe diameter by a distance equal to
1/2 of the pipe radius (see
below). Notice that the 1/2 radius offset can be applied either above or below the
horizontal pipe diameter.
Note:
As the installation procedures are identical, the instructions in this section will show the
MR1 Top Mid-Radius
configuration only, as an example.
Figure 24: MR1 Mid-Radius Path Configurations
The
MR1 Mid-Radius
path nozzle installation procedure includes the following steps:
1.
“Identifying the Nozzle Installation Kit Components - MR1 Mid-Radius” on page 19
2.
“Selecting and Marking the First Nozzle Location - MR1 Mid-Radius” on page 20
3.
“Determining and Marking the Second Nozzle Location - MR1 Mid-Radius” on page 24
4.
“Installing the First Welding Boss - MR1 Mid-Radius” on page 29
5.
“Installing the First Nozzle - MR1 Mid-Radius” on page 32
6.
“Installing the Second Welding Boss and Nozzle MR1 Mid-Radius” on page 34
7.
Proceed to one of the following:
•
“Hot Tapping the Pipe - MR1 Mid-Radius” on page 35
•
“Cold Tapping the Pipe - MR1 Mid-Radius” on page 35
CAUTION!
There are two different variations of the mid-radius nozzle installation. These are named
the
MR1
configuration, which uses p/n
591-338
bosses, and the
MR2
configuration, which uses
p/n
591-516
bosses. It is critical that you use the correct mid-radius configuration for the nozzles you
have been provided. Failure to do so will severely degrade the accuracy of your system.
CAUTION!
The instructions in this section are for the
MR1 Mid-Radius
path configuration only. If your
Nozzle Installation Kit
is for an
MR2 Mid-Radius
path, proceed immediately to
MR2 Mid-Radius Path” on page 36
FLOW
FLOW
MR1 Top Mid-Radius
MR1 Bottom Mid-Radius
Top View
Top View
End View
End View
Содержание T17
Страница 1: ...GE Oil Gas Flow 916 128 Rev D September 2020 Model T17 Ultrasonic Flow Transducer Installation Guide ...
Страница 2: ......
Страница 4: ...ii no content intended for this page ...
Страница 62: ...Chapter 2 Installing the Pipe Nozzles 54 Model T17 Installation Guide no content intended for this page ...
Страница 64: ...Chapter 3 Installing an Isolation Valve 56 Model T17 Installation Guide no content intended for this page ...
Страница 88: ...Chapter 6 Specifications 80 Model T17 Installation Guide no content intended for this page ...
Страница 90: ...Warranty 82 Model T17 Installation Guide no content intended for this page ...
Страница 92: ......
Страница 93: ......