Chapter 2. Installation
32
PanaFlow™ MV80 & MV82 User’s Manual
2.5 Loop Power Flowmeter Wiring Connections
The Type 4X enclosure contains an integral wiring compartment with one dual strip terminal block located in the
smaller end of the enclosure (see
below). Two 3/4-inch female NPT conduit entries are available for separate
power and signal wiring. For all hazardous area installations, make sure to use an agency-approved fitting at each
conduit entry. If conduit seals are used, they must be installed within 18 inches (457 mm) of the enclosure.
Figure 19: Loop Power Wiring Terminals
WARNING!
To avoid potential electric shock, follow National Electric Code safety practices or your
local code when wiring this unit to a power source and to peripheral devices. Failure to do so could
result in injury or death. All wiring procedures must be performed with the power off.
+ – + –
+ –
Loop
Power
Pulse
Output
Power
+ –
Freq.
Output
Содержание PanaFlow MV80
Страница 2: ......
Страница 12: ...Contents x PanaFlow MV80 MV82 User s Manual no content intended for this page ...
Страница 20: ...Chapter 1 Introduction 8 PanaFlow MV80 MV82 User s Manual no content intended for this page ...
Страница 62: ...Chapter 2 Installation 50 PanaFlow MV80 MV82 User s Manual no content intended for this page ...
Страница 120: ...Chapter 4 Serial Communications 108 PanaFlow MV80 MV82 User s Manual no content intended for this page ...
Страница 148: ...Appendix B Approvals 136 PanaFlow MV80 MV82 User s Manual no content intended for this page ...
Страница 158: ...Appendix D Glossary 146 PanaFlow MV80 MV82 User s Manual no content intended for this page ...
Страница 160: ...Warranty 148 PanaFlow MV80 MV82 User s Manual no content intended for this page ...
Страница 162: ... no content intended for this page ...
Страница 163: ......