GEK-113000AE
F650 Digital Bay Controller
D-3
APPENDIX D
D.1 FACTORY DEFAULT SETTINGS
D
PRODUCT SETUP>COMMUNICATION SETTINGS >DNP3 SLAVE
DNP3 SLAVE 1 > DNP3 SLAVE 2 > DNP3 SLAVE 3
SETTING DESCRIPTION
NAME
DEFAULT VALUE
STEP
RANGE
USER
VALUE
Communications port assigned to the
DNP protocol
Physical Port
NONE
N/A
[COM1:COM2:NETWORK]
DNP slave address
Address
255
N/A
[0 : 65534]
1st Octect of IP address of DNP
master 1
IP Addr Client1 Oct1
0
N/A
[0 : 255]
2nd Octect of IP address of DNP
master 1
IP Addr Client1 Oct2
0
N/A
[0 : 255]
3nd Octect of IP address of DNP
master 1
IP Addr Client1 Oct3
0
N/A
[0 : 255]
4th Octect of IP address of DNP
master 1
IP Addr Client1 Oct4
0
N/A
[0 : 255]
1st Octect of IP address of DNP
master 2
IP Addr Client2 Oct1
0
N/A
[0 : 255]
2nd Octect of IP address of DNP
master 2
IP Addr Client2 Oct2
0
N/A
[0 : 255]
3nd Octect of IP address of DNP
master 2
IP Addr Client2 Oct3
0
N/A
[0 : 255]
4th Octect of IP address of DNP
master 2
IP Addr Client2 Oct4
0
N/A
[0 : 255]
1st Octect of IP address of DNP
master 3
IP Addr Client3 Oct1
0
N/A
[0 : 255]
2nd Octect of IP address of DNP
master 3
IP Addr Client3 Oct2
0
N/A
[0 : 255]
3nd Octect of IP address of DNP
master 3
IP Addr Client3 Oct3
0
N/A
[0 : 255]
4th Octect of IP address of DNP
master 3
IP Addr Client3 Oct4
0
N/A
[0 : 255]
1st Octect of IP address of DNP
master 4
IP Addr Client4 Oct1
0
N/A
[0 : 255]
2nd Octect of IP address of DNP
master 4
IP Addr Client4 Oct2
0
N/A
[0 : 255]
3nd Octect of IP address of DNP
master 4
IP Addr Client4 Oct3
0
N/A
[0 : 255]
4th Octect of IP address of DNP
master 4
IP Addr Client4 Oct4
0
N/A
[0 : 255]
1st Octect of IP address of DNP
master 4
IP Addr Client5 Oct1
0
N/A
[0 : 255]
2nd Octect of IP address of DNP
master 4
IP Addr Client5 Oct2
0
N/A
[0 : 255]
3nd Octect of IP address of DNP
master 4
IP Addr Client5 Oct3
0
N/A
[0 : 255]
4th Octect of IP address of DNP
master 4
IP Addr Client5 Oct4
0
N/A
[0 : 255]
TCP/UDP port number for DNP over
Ethernet
TCP/UDP Port
20000
N/A
[0 : 65535]
Unsolicited responses permission
Unsol Resp Function
DISABLED
N/A
[DISABLED – ENABLED]
Time out to confirm an unsolicited
response
Unsol Resp TimeOut
5
1 s
[0 : 60]
Number of retransmissions of an unsol
resp w/o confirmation
Unsol Resp Max Ret
10
N/A
[0 : 255]
Address to which all unsolicited
responses are sent
Unsol Resp Dest Adr
200
N/A
[0 : 65519]
Scale for currents
Current Scale Factor
1
N/A
[0.00001-0.0001-0.001-
0.01-0.1-1-10-100-1000]
Scale for voltages
Voltage Scale Factor
1
N/A
[0.00001-0.0001-0.001-
0.01-0.1-1-10-100-1000]
Содержание Multilin F650
Страница 66: ...2 38 F650 Digital Bay Controller GEK 113000AE 2 6 EXTERNAL CONNECTIONS 2 PRODUCT DESCRIPTION 2...
Страница 210: ...6 28 F650 Digital Bay Controller GEK 113000AE 6 18 THERMAL IMAGE ELEMENT 49 6 COMMISSIONING 6...
Страница 216: ...7 6 F650 Digital Bay Controller GEK 113000AE 7 4 RELAY CONFIGURATION 7 FREQUENTLY ASKED QUESTIONS 7...
Страница 256: ...A 36 F650 Digital Bay Controller GEK 113000AE A 1 LOGIC OPERANDS APPENDIX A A...
Страница 270: ...B 14 F650 Digital Bay Controller GEK 113000AE B 3 LINK LOSS ALERT LLA APPENDIX B B...
Страница 272: ...GEK 113000AE F650 Digital Bay Controller C 2 APPENDIX C C 1 FACTORY DEFAULT LOGIC C...
Страница 273: ...GEK 113000AE F650 Digital Bay Controller C 3 APPENDIX C C 1 FACTORY DEFAULT LOGIC C...
Страница 275: ...GEK 113000AE F650 Digital Bay Controller C 5 APPENDIX C C 1 FACTORY DEFAULT LOGIC C...
Страница 276: ...GEK 113000AE F650 Digital Bay Controller C 6 APPENDIX C C 1 FACTORY DEFAULT LOGIC C...
Страница 279: ...GEK 113000AE F650 Digital Bay Controller C 9 APPENDIX C C 1 FACTORY DEFAULT LOGIC C...
Страница 280: ...GEK 113000AE F650 Digital Bay Controller C 10 APPENDIX C C 1 FACTORY DEFAULT LOGIC C...
Страница 281: ...GEK 113000AE F650 Digital Bay Controller C 11 APPENDIX C C 1 FACTORY DEFAULT LOGIC C...