GEK-113000AE
F650 Digital Bay Controller
2-31
2 PRODUCT DESCRIPTION
2.5 TECHNICAL SPECIFICATIONS
2
Protocols available:
ModBus
®
RTU / DNP 3.0/IEC103
Typical distance:
1200 m for cooper cable, 1000 m for glass fiber and 50 m for
plastic fiber
Isolation:
2 kV
CAN PORT:
Rear port:
CAN port in models C, M, X, Y, Z for asynchronous rear ports
Type:
Multimode glass F.O. port with ST connectors
Fiber Wave length:
820 nm
Fiber type:
multimode 62.5/125
μ
m or 50/125
μ
m
Maximum recommended length
300m for cooper cable and glass fiber
Isolation:
2 kV
ETHERNET PORT:
Rear port:
For models B, C, D, E
ETH_1/ ETH_2
For models G,H,J,K,L,M
ETH_E/ ETH_A/ ETH_B
Type (depending on model):
Model B:
10/100BaseTX self-negotiable
Model C:
10/100 100Base FX
Model D:
10/100 redundant 100BaseFX (Physical media redundancy)
Model E:
Redundant 10/100BaseTX self-negotiable ports
Model G:
1588, 10/100 Base TX* + 100 Base TX
Model H:
1588, 10/100 Base TX* + 100 Base FX
Model J:
PRP, 1588, 10/100 Base TX* + Redundant 100 Base FX
Model K:
PRP, HSR, RSTP, 1588, 10/100 Base TX* + Redundant 100 Base FX
Model L:
PRP, 1588, 10/100 Base TX* + Redundant 100 Base TX
Model M:
PRP, HSR, RSTP, 1588, 10/100 Base TX* + Redundant 100 Base TX
NOTE: (*) This Ethernet port (ETH_E) is intended only for maintenance purpose.
10/100BaseTX
RJ45 connector
100BaseFX
ST connectors
Wave length:
1300 nm
Fiber type:
multimode 62.5/125 . m or 50/125 . m
Protocols available:
ModBus® TCP/IP
DNP over TCP/IP and UDP/IP
IEC 61850
Http, ftp, tftp (allow the use of a standard Internet browser)
Typical distance:
1000 m for glass fiber and 150 m for RJ45 cable
Response time to ModBus commands:
10 ms Typical
Isolation:
2 kV
In Models C and D, the 10/100BaseTX port is selected by an internal switch (see 3.3.3)
Two witness LED’s for transmission and reception are included
SIMPLE NETWORK TIME PROTOCOL (SNTP)
Clock synchronization error:
<10 ms (typical)
PRECISION TIME PROTOCOL (PTP)
PTP IEEE Std 1588 2008 (version 2)
Power Profile (PP) per IEEE Standard PC37.238TM2011
Slave-only ordinary clock
Содержание Multilin F650
Страница 66: ...2 38 F650 Digital Bay Controller GEK 113000AE 2 6 EXTERNAL CONNECTIONS 2 PRODUCT DESCRIPTION 2...
Страница 210: ...6 28 F650 Digital Bay Controller GEK 113000AE 6 18 THERMAL IMAGE ELEMENT 49 6 COMMISSIONING 6...
Страница 216: ...7 6 F650 Digital Bay Controller GEK 113000AE 7 4 RELAY CONFIGURATION 7 FREQUENTLY ASKED QUESTIONS 7...
Страница 256: ...A 36 F650 Digital Bay Controller GEK 113000AE A 1 LOGIC OPERANDS APPENDIX A A...
Страница 270: ...B 14 F650 Digital Bay Controller GEK 113000AE B 3 LINK LOSS ALERT LLA APPENDIX B B...
Страница 272: ...GEK 113000AE F650 Digital Bay Controller C 2 APPENDIX C C 1 FACTORY DEFAULT LOGIC C...
Страница 273: ...GEK 113000AE F650 Digital Bay Controller C 3 APPENDIX C C 1 FACTORY DEFAULT LOGIC C...
Страница 275: ...GEK 113000AE F650 Digital Bay Controller C 5 APPENDIX C C 1 FACTORY DEFAULT LOGIC C...
Страница 276: ...GEK 113000AE F650 Digital Bay Controller C 6 APPENDIX C C 1 FACTORY DEFAULT LOGIC C...
Страница 279: ...GEK 113000AE F650 Digital Bay Controller C 9 APPENDIX C C 1 FACTORY DEFAULT LOGIC C...
Страница 280: ...GEK 113000AE F650 Digital Bay Controller C 10 APPENDIX C C 1 FACTORY DEFAULT LOGIC C...
Страница 281: ...GEK 113000AE F650 Digital Bay Controller C 11 APPENDIX C C 1 FACTORY DEFAULT LOGIC C...