GEK-106310AE
F650 Digital Bay Controller
3-27
3 HUMAN INTERFACES. SETTINGS & ACTUAL VALUES 3.1 ENERVISTA 650 SETUP SOFTWARE INTERFACE
3
3.1.8.8 RELAY CONFIGURATION
This is the relay configuration section in which the relay can be configured using internal states or already compiled
equation on PLC Editor.
Table 3.17: GENERAL OVERVIEW OF RELAY CONFIGURATION MENU:
RELAY CONFIG
Outputs
Configuration of contact output operate and reset signals for all boards.
LEDs
15 LEDs fully configurable from any logical variable, contact or virtual
input. First 5
LEDs are latched by hardware, the rest are self-reset but
can be latched through PLC configuration. For firmware version 7.20 and
higher, all 15 LEDs could be latched by setting. From the LED
configuration screen, it is possible to print the vertical LED label for the
relay.
Operations
Configurable operations up to 24. Operation texts, interlocks, final states,
frontal keys, time outs and masters.
Protection Elements
This tab allows assigning operands (logic signals) as inputs to different
protection elements. To block, reset, initiate the different protection
elements inputs.
Control Elements
This tab allows assigning operands (logic signals) as inputs to different
control elements.
Oscillography
Trigger and up to 16 digital channels to be included in oscillography
records, are programmable from any logical variable, contact or virtual
input. Text configuration is only for off-line mode.
NOTE:
This screen is used for the configuration of digital channels and
oscillography trigger. The rest of parameters, such as function enabling/
disabling, sampling rate, number of oscillography files, etc. must be set
on the
Setpoint>Product Setup>Oscillography
menu.
Control Events
Up to 128 user programmable events from any logical variable, contact
or virtual input. Possibility to display the event as an alarm on the alarms
panel. Control events are also displayed in the snapshot events
recording. 1 ms time tagging.
A control event is a logic signal associated to an operand or combination
of operands, that allows following the status of that signal.
Switchgear
Up to 16 configurable switchgear elements. A switchgear element can be
a breaker, a line selector switch, a grounding selector switch, a busbar
selector switch, etc. This screen allows configuration of type of contacts,
opening and closing time, contact assignation and text for events related
to switchgear. There are 64 pre-established events for switchgear, which
correspond to opening, closing, Error01 and Error11 of the 16
programmable switchgear elements.
Remote outputs
Up to 32 DNA bits and 64 user St bits to be transmitted to remote devices
over CAN using GSSE messages
Inputs
Text configuration for off-line mode file management for all the contact
inputs available in device.
Virtual Inputs
Text configuration for off-line mode file management. 32 latched and 32
self reset virtual inputs.
MMI (HMI-Human
Machine Interface)
Screen one line diagram configuration. This menu shows a canvas to
draw a simplified one-line diagram of a bay in a feeder, line, transformer,
etc. The menu includes a library for power elements, metering elements,
text and drawings. See an example on the next page.
Содержание Multilin F650
Страница 66: ...2 38 F650 Digital Bay Controller GEK 113000AE 2 6 EXTERNAL CONNECTIONS 2 PRODUCT DESCRIPTION 2...
Страница 210: ...6 28 F650 Digital Bay Controller GEK 113000AE 6 18 THERMAL IMAGE ELEMENT 49 6 COMMISSIONING 6...
Страница 216: ...7 6 F650 Digital Bay Controller GEK 113000AE 7 4 RELAY CONFIGURATION 7 FREQUENTLY ASKED QUESTIONS 7...
Страница 256: ...A 36 F650 Digital Bay Controller GEK 113000AE A 1 LOGIC OPERANDS APPENDIX A A...
Страница 270: ...B 14 F650 Digital Bay Controller GEK 113000AE B 3 LINK LOSS ALERT LLA APPENDIX B B...
Страница 272: ...GEK 113000AE F650 Digital Bay Controller C 2 APPENDIX C C 1 FACTORY DEFAULT LOGIC C...
Страница 273: ...GEK 113000AE F650 Digital Bay Controller C 3 APPENDIX C C 1 FACTORY DEFAULT LOGIC C...
Страница 275: ...GEK 113000AE F650 Digital Bay Controller C 5 APPENDIX C C 1 FACTORY DEFAULT LOGIC C...
Страница 276: ...GEK 113000AE F650 Digital Bay Controller C 6 APPENDIX C C 1 FACTORY DEFAULT LOGIC C...
Страница 279: ...GEK 113000AE F650 Digital Bay Controller C 9 APPENDIX C C 1 FACTORY DEFAULT LOGIC C...
Страница 280: ...GEK 113000AE F650 Digital Bay Controller C 10 APPENDIX C C 1 FACTORY DEFAULT LOGIC C...
Страница 281: ...GEK 113000AE F650 Digital Bay Controller C 11 APPENDIX C C 1 FACTORY DEFAULT LOGIC C...