GEK-113000AE
F650 Digital Bay Controller
D-23
APPENDIX D
D.1 FACTORY DEFAULT SETTINGS
D
SETPOINT > PROTECTION ELEMENTS > POWER > DIRECTIONAL POWER>
DIRECTIONAL POWER 1> DIRECTIONAL POWER 2 > DIRECTIONAL POWER 3
SETTING DESCRIPTION
NAME
DEFAULT VALUE
STEP
RANGE
USER
VALUE
Function permission
Function
DISABLED
N/A
[DISABLED – ENABLED]
Block from off-line
Blk Time After Close
0.00
0.01 s
[0.00 : 900.00]
Directional Angle for stage 1
Dir Power Angle 1
0.00
0.01 Deg
[0.00 : 359.99]
Pickup level for stage 1
Stage 1 Tap
10.00
0.01MW
[-10000.00 : 10000.00]
Trip time for stage 1
Stage 1 Time
60.00
0.01 s
[0.00 : 900.00]
Directional Angle for stage 2
Dir Power Angle 2
0.00
1 Deg
[0.00 : 359.99]
Pickup level for stage 2
Stage 2 Tap
20.00
0.01MW
[-10000.00 : 10000.00]
Trip time for stage 2
Stage 2 Time
60.00
0.01 s
[0.00 : 900.00]
Snapshot Event generation
Snapshot Events
ENABLED
N/A
[DISABLED – ENABLED]
SETPOINT > PROTECTION ELEMENTS > POWER
WATT GND FLT HIGH 1> WATT GND FLT HIGH 2 > WATT GND FLT HIGH 3
WATT GND FLT LOW 1> WATT GND FLT LOW 2 > WATT GND FLT LOW 3
SETTING DESCRIPTION
NAME
DEFAULT VALUE
STEP
RANGE
USER
VALUE
Function permission
Function
DISABLED
N/A
[DISABLED-ENABLED]
Supervision minimum voltage
Voltage Pickup Level
2
0.01 V
[2.00 : 70.00]
Source of operating current.
Current selection
IN
N/A
[IN-IG]
Pickup Level for Overcurrent
OC Pickup Level
0,005
0.001A
[0.005 : 0.400]
Pickup Delay for Overcurrent
OC Pickup Delay
0,2
0.01 s
[0.00 : 600.00]
Pickup Level for operating Power
Power Pickup
0,01
0.01 W
[0.01 : 4.50]
Max torque angle
MTA
0
1 Deg
[0 : 360]
Pickup Delay for Operating Power
Power Pickup Delay
0,2
0.01 s
[0.00 : 600.00]
Curve shape
Curve
DEFINITE TIME
N/A
[DEFINITE TIME -
INVERSE TIME - USER
CURVE A - USER CURVE
B - USER CURVE C -
USER CURVE D]
Multiplier
Multiplier
1
0.01 s
[0.02 : 2.00]
Snapshot event generation
Snapshot Event
DISABLED
N/A
[DISABLED-ENABLED]
SETPOINT > CONTROL ELEMENTS > SETTING GROUP
SETTING DESCRIPTION
NAME
DEFAULT VALUE
STEP
RANGE
USER
VALUE
Setting Grouping Permission
Function
DISABLED
N/A
[DISABLED – ENABLED]
Active Group
Active Group
GROUP 1
N/A
[GROUP 1 – GROUP 2 –
GROUP 3]
Snapshot Event generation
Snapshot Events
ENABLED
N/A
[DISABLED – ENABLED]
SETPOINT > CONTROL ELEMENTS > UNDERFREQUENCY
UNDERFREQUENCY 1 > UNDERFREQUENCY 2 > UNDERFREQUENCY 3
SETTING DESCRIPTION
NAME
DEFAULT VALUE
STEP
RANGE
USER
VALUE
Function permission
Function
DISABLED
N/A
[DISABLED – ENABLED]
Pickup level
Pickup Level
49.50
0.01 Hz
[20.00 : 65.00]
Trip time
Trip Delay
0.00
0.01 s
[0.00 : 900.00]
Reset time
Reset Delay
0.00
0.01 s
[0.00 : 900.00]
Minimum voltage threshold
Minimum Voltage
30
1 V
[10 : 300]
Snapshot event generation
Snapshot Events
ENABLED
N/A
[DISABLED – ENABLED]
Содержание Multilin F650
Страница 66: ...2 38 F650 Digital Bay Controller GEK 113000AE 2 6 EXTERNAL CONNECTIONS 2 PRODUCT DESCRIPTION 2...
Страница 210: ...6 28 F650 Digital Bay Controller GEK 113000AE 6 18 THERMAL IMAGE ELEMENT 49 6 COMMISSIONING 6...
Страница 216: ...7 6 F650 Digital Bay Controller GEK 113000AE 7 4 RELAY CONFIGURATION 7 FREQUENTLY ASKED QUESTIONS 7...
Страница 256: ...A 36 F650 Digital Bay Controller GEK 113000AE A 1 LOGIC OPERANDS APPENDIX A A...
Страница 270: ...B 14 F650 Digital Bay Controller GEK 113000AE B 3 LINK LOSS ALERT LLA APPENDIX B B...
Страница 272: ...GEK 113000AE F650 Digital Bay Controller C 2 APPENDIX C C 1 FACTORY DEFAULT LOGIC C...
Страница 273: ...GEK 113000AE F650 Digital Bay Controller C 3 APPENDIX C C 1 FACTORY DEFAULT LOGIC C...
Страница 275: ...GEK 113000AE F650 Digital Bay Controller C 5 APPENDIX C C 1 FACTORY DEFAULT LOGIC C...
Страница 276: ...GEK 113000AE F650 Digital Bay Controller C 6 APPENDIX C C 1 FACTORY DEFAULT LOGIC C...
Страница 279: ...GEK 113000AE F650 Digital Bay Controller C 9 APPENDIX C C 1 FACTORY DEFAULT LOGIC C...
Страница 280: ...GEK 113000AE F650 Digital Bay Controller C 10 APPENDIX C C 1 FACTORY DEFAULT LOGIC C...
Страница 281: ...GEK 113000AE F650 Digital Bay Controller C 11 APPENDIX C C 1 FACTORY DEFAULT LOGIC C...