5-2
F650 Digital Bay Controller
GEK-113000AE
5.1 UPGRADE FROM VERSION BELOW V7.00.
5 BOOTCODE AND FIRMWARE UPGRADE
5
5.1.1 COMMUNICATION PARAMETERS
1.
Ethernet Connection/Type - Both boot code and firmware upgrade processes require Ethernet communications. It is
strongly recommended to use a direct connection between the PC and the relay using a Cross-Over RJ45 Ethernet
cable, instead a direct connection through a hub or switch. Upgrading through Local Area Network (LAN) must be
avoided.
Serial RS232 Communication - Serial communication is necessary only to perform the bootware upgrade for versions
previous to 7.00.
2.
Relay IP Address - And IP address must be assigned to the relay in the Ethernet parameters via HMI at
PRODUCT
SETUP>COMMUNICATION>ETHERNET>ETHERNET1
menu or via Enervista 650 Setup at
SETPOINT>PRODUCT
SETUP>COMMUNICATION SETTINGS>NETWORK (Ethernet) 1
as shown in the table below:
Table 5–1: ETHERNET PARAMETERS
3.
PC IP Address - In case the boot code has been previously updated to the relay (section 9.2), the IP address and other
parameters already assigned in the process will be:
IP Address:192.168.37.177
Netmask:255.255.255.0
Gateway:192.168.37.10
Then the PC settings should be the same pattern as follows:
RELAYS WITH FIBER OPTIC ETHERNET
The upgrade of the boot program (BOOTCODE) must be performed by crossed Ethernet copper cable connected to the
PC. It is not necessary to change the internal switch from fiber to RJ45, because the upgrade is made at 10Mb/s.
This does not apply to the firmware upgrade, which can be done either via Ethernet Fiber connection, or through the
RJ45 cable connection.
For upgrading firmware versions lower than 3.20 or upgrading bootware, be aware to calibrate the unit offset, after
upgrading it, on Communication --> Calibration --> Offset Calibration . No analog currents nor analog voltages must be
injected in the unit during this process.
PRODUCT SETUP>COMMUNICATION SETTINGS >NETWORK (ETHERNET) 1
NAME
VALUE
UNITS
RANGE
IP Address Oct1
192
[0 : 255]
IP Address Oct2
168
[0 : 255]
IP Address Oct3
37
[0 : 255]
IP Address Oct4
177
[0 : 255]
Netmask Oct1
255
[0 : 255]
Netmask Oct2
255
[0 : 255]
Netmask Oct3
255
[0 : 255]
Netmask Oct4
0
[0 : 255]
Gateway IP Oct1
192
[0 : 255]
Gateway IP Oct2
168
[0 : 255]
Gateway IP Oct3
37
[0 : 255]
Gateway IP Oct4
10
[0 : 255]
Содержание Multilin F650
Страница 66: ...2 38 F650 Digital Bay Controller GEK 113000AE 2 6 EXTERNAL CONNECTIONS 2 PRODUCT DESCRIPTION 2...
Страница 210: ...6 28 F650 Digital Bay Controller GEK 113000AE 6 18 THERMAL IMAGE ELEMENT 49 6 COMMISSIONING 6...
Страница 216: ...7 6 F650 Digital Bay Controller GEK 113000AE 7 4 RELAY CONFIGURATION 7 FREQUENTLY ASKED QUESTIONS 7...
Страница 256: ...A 36 F650 Digital Bay Controller GEK 113000AE A 1 LOGIC OPERANDS APPENDIX A A...
Страница 270: ...B 14 F650 Digital Bay Controller GEK 113000AE B 3 LINK LOSS ALERT LLA APPENDIX B B...
Страница 272: ...GEK 113000AE F650 Digital Bay Controller C 2 APPENDIX C C 1 FACTORY DEFAULT LOGIC C...
Страница 273: ...GEK 113000AE F650 Digital Bay Controller C 3 APPENDIX C C 1 FACTORY DEFAULT LOGIC C...
Страница 275: ...GEK 113000AE F650 Digital Bay Controller C 5 APPENDIX C C 1 FACTORY DEFAULT LOGIC C...
Страница 276: ...GEK 113000AE F650 Digital Bay Controller C 6 APPENDIX C C 1 FACTORY DEFAULT LOGIC C...
Страница 279: ...GEK 113000AE F650 Digital Bay Controller C 9 APPENDIX C C 1 FACTORY DEFAULT LOGIC C...
Страница 280: ...GEK 113000AE F650 Digital Bay Controller C 10 APPENDIX C C 1 FACTORY DEFAULT LOGIC C...
Страница 281: ...GEK 113000AE F650 Digital Bay Controller C 11 APPENDIX C C 1 FACTORY DEFAULT LOGIC C...