2–20
MM3 MOTOR MANAGER 3 – INSTRUCTION MANUAL
STARTER TYPES
CHAPTER 2: INSTALLATION
2.4.6
Inverter
Starter
When the RUN contact closes the inverter ramps up the motor to the programmed speed.
When the RUN contact opens, the inverter ramps down the motor to a stop.
Figure 2-16: Elementary Inverter Starter
To program the MM3 Motor Manager 3 for inverter starter, set:
S1 CONFIGURATION
ÖØ
STARTER
Ö
STARTER TYPE
: INVERTER
S1 CONFIGURATION
ÖØ
STARTER
ÖØ
RAMP UP TIME
: 1 to 125 sec.
S1 CONFIGURATION
ÖØ
STARTER
ÖØ
RAMP DOWN TIME
: 1 to 125 sec.
The
RAMP UP TIME
and
RAMP DOWN TIME
setpoints appear when the
STARTER TYPE
is
selected as “INVERTER”. See the next section for details on functionality.
Start sequence:
1.
Start command is received by the MM3 Motor Manager 3. (serial, switch input
or faceplate).
2.
Close and maintain contactor A output relay. - provide power to the inverter
3.
Wait for one second.
4.
Close and maintain contactor B output relay. - signal the inverter to start the
motor.
5.
Wait for the
RAMP UP TIME
for Contactor B Status N.O. to close.
Stop/trip sequence:
1.
Stop command is received or a trip occurs. (serial, switch input or faceplate)
2.
Open contactor B output relay.
3.
Wait for the
RAMP DOWN TIME
for Contactor B Status N.O. to open.
4.
When Contactor B Status N.O. reads open, open contactor A output relay.
If feedback is not received from the 1M contact to the Contactor A Status N.O. input within
1 second of closing Contactor A output relay, an open control circuit alarm occurs. This
causes the Contactor A and B output relays to open.
If Contactor B Status N.O. does not receive feedback from the up to speed contact on the
inverter within the RAMP UP TIME setpoint during a start, a DRIVE FAILED TO START alarm
will be generated. If Contactor B Status N.O. feedback remains at the MM3 Motor Manager
3 after the
RAMP DOWN TIME
has expired during a stop, a drive failed to stop alarm will be
generated.
If feedback remains at Contactor A Status N.O. input more than one second after opening
the contactor A output relay, a welded contactor alarm will occur.
Содержание MM3
Страница 8: ...vi MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 11: ...CHAPTER 1 INTRODUCTION OVERVIEW MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL 1 3 Figure 1 1 Functional block diagram ...
Страница 18: ...1 10 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL TECHNICAL SPECIFICATIONS CHAPTER 1 INTRODUCTION ...
Страница 80: ...4 18 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL CHASSIS MOUNT UNITS CHAPTER 4 SOFTWARE ...
Страница 124: ...5 44 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL S7 TESTING CHAPTER 5 SETPOINTS ...
Страница 198: ...8 54 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL MODBUS MEMORY MAP CHAPTER 8 COMMUNICATIONS ...
Страница 220: ...10 14 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL GE MULTILIN WARRANTY CHAPTER 10 MISCELLANEOUS ...