5–40
MM3 MOTOR MANAGER 3 – INSTRUCTION MANUAL
S7 TESTING
CHAPTER 5: SETPOINTS
• MM3 Motor Manager 3 is tripped
When
SIMULATION
is turned on, the
CURRENT SIMULATION HAS BEEN ENABLED
flash
message is displayed for 3 seconds. When
SIMULATION
is turned off, the
CURRENT
SIMULATION HAS BEEN DISABLED
flash message is displayed for 3 seconds.
•
SIMULATION ENABLED FOR
: Select the desired length of time that simulation will be
enabled. When the programmed time has elapsed, current simulation will turn off. If
“UNLIMITED” is selected, simulated current will be used until one of the above
mentioned conditions is met.
•
PHASE A/B/C CURRENT
: Enter the desired phase current for simulation. For example,
to verify operation of the unbalance function. Enter the following simulation values
assuming
S2 PROTECTION
Ö
MOTOR PROTECTION THERMAL
Ö
FULL LOAD CURRENT
is
“100 A” to create an unbalance of 40%.
I
a
= 100 A,
I
b
= 80 A,
I
c
= 150 A
Now set
SIMULATION
to “ON”. The relay will see this simulated current in all three phases
instead of the actual input current. The MM3 Motor Manager 3 should trip after a 5 second
delay. Set
SIMULATION
to “OFF” after testing is complete.
•
GROUND CURRENT
: Enter the ground current for simulation of a ground fault.
Set
SIMULATION
to “ON”
to see the effect of this current.
5.8.4
Analog Output
Simulation
PATH: S7 TESTING
ÖØ
ANALOG OUTPUT SIMULATION
The analog output simulation settings are programmed as follows:
•
SIMULATION
: Enter ON to switch from actual analog output to the programmed
simulation value. Set this setpoint to OFF after simulation is complete. As a safeguard,
simulation will automatically turn off if:
• power to the MM3 Motor Manager 3 is turned off and on
• time programmed in
SIMULATION ENABLED FOR
has elapsed since simulation was
first enabled
When analog output simulation is turned on the
A/O SIMULATION HAS BEEN ENABLED
flash
message will be displayed for 3 seconds. When analog output simulation is turned off the
A/O SIMULATION HAS BEEN DISABLED
flash message will be displayed for 3 seconds.
•
SIMULATION ENABLED FOR
: Select the desired length of time to enable simulation.
When the programmed time has elapsed, analog output simulation will turn off. If
“UNLIMITED” is selected, simulated analog output will be used until simulation is
turned off via the
SIMULATION
setpoint or via the serial port or until control power is
removed from the MM3 Motor Manager 3.
•
ANALOG OUTPUT FORCED TO
: Enter in percent the analog output value to be
simulated. For example, setting
ANALOG OUTPUT FORCED TO
to “50.0%” and
SIMULATION
to “ON”, the output current level will be 12 mA.
] ANALOG OUTPUT
] SIMULATION
SIMULATION:
OFF
Range: ON, OFF
SIMULATION ENABLED
FOR:
15 min.
Range: 5 to 300 min. or UNLIMITED in
steps of 5
ANALOG OUTPUT FORCED
TO:
OFF %
Range: 0 to 120% or OFF in steps of 1
Содержание MM3
Страница 8: ...vi MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 11: ...CHAPTER 1 INTRODUCTION OVERVIEW MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL 1 3 Figure 1 1 Functional block diagram ...
Страница 18: ...1 10 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL TECHNICAL SPECIFICATIONS CHAPTER 1 INTRODUCTION ...
Страница 80: ...4 18 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL CHASSIS MOUNT UNITS CHAPTER 4 SOFTWARE ...
Страница 124: ...5 44 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL S7 TESTING CHAPTER 5 SETPOINTS ...
Страница 198: ...8 54 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL MODBUS MEMORY MAP CHAPTER 8 COMMUNICATIONS ...
Страница 220: ...10 14 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL GE MULTILIN WARRANTY CHAPTER 10 MISCELLANEOUS ...