CHAPTER 8: COMMUNICATIONS
MODBUS MEMORY MAP
MM3 MOTOR MANAGER 3 – INSTRUCTION MANUAL
8–31
44356
4355
1103
Analog input units
characters 3 and 4
32 to
127
1
ASCII
F10
"IT"
44357
4356
1104
Analog input units
characters 5 and 6
32 to
127
1
ASCII
F10
"S "
44358
4357
1105
Analog input units
characters 7 and 8
32 to
127
1
ASCII
F10
44359
4358
1106
Analog input units
characters 9 and 10
32 to
127
1
ASCII
F10
44360
4359
1107
Analog input minimum
scale
0 to
20000
10
---
F1
0
44361
4360
1108
Analog input maximum
scale
10 to
20000
10
---
F1
1000
44362
4361
1109
Analog alarm low level
1 to
20001
1
---
F1*
65535 =
OFF
44363
4362
110A
Analog alarm low delay
1 to
600
1
s
F1
5
44364
4363
110B
Analog alarm high level
1 to
20001
1
---
F1*
65535 =
OFF
44365
4364
110C
Analog alarm high delay
1 to
600
1
s
F1
5
44366
4365
110D
Analog trip low level
1 to
20001
1
---
F1*
65535 =
OFF
44367
4366
110E
Analog trip low delay
1 to
600
1
s
F1
5
44368
4367
110F
Analog trip high level
1 to
20001
1
---
F1*
65535 =
OFF
44369
4368
1110
Analog trip high delay
1 to
600
1
s
F1
5
44370
4369
1111
Analog low override delay
1 to
126
1
s
F1*
5
44371
4370
1112
Analog high override delay
1 to
126
1
s
F1*
5
44372
4371
1113
Analog output type
0 to 5
1
---
F38
0 = NOT
USED
44373
4372
1114
...Reserved...
...
...
...
...
...
Analog output simulation (read/write setpoints)
44374
4373
1115
Analog output simulation
0 to 1
1
F37
0 = 0FF
44375
4374
1116
Force analog output
0 to
1201
1
0.10
%
F1**
0
44376
4375
1117
Analog output simulation
period
5 to
305
5
min.
F1**
15 min.
44377
4376
1118
...Reserved...
...
...
...
...
...
44378
4377
1119
...Reserved...
...
...
...
...
...
Analog input simulation (read/write setpoints)
44379
4378
111A
Analog input simulation
0 to 1
1
F37
0 = OFF
44380
4379
111B
Analog input value
40 to
201
1
F1*
65535 =
OFF
44381
4380
111C
Analog input simulation
period
5 to
305
5
F1**
15 min.
Table 8–2: Modbus Memory Map (Sheet 16 of 28)
Modicon
Address
Description
Range
Step
Units Format
Default
dec.
hex
* – Maximum setpoint value and 65535 represent OFF; ** – 1/phase current scale factor
×
A; *** – 101
represents unlimited;
† – Minimum setpoint value represents OFF; ~ – 0.1
×
A when high resolution mode is disabled;
0.01
×
A when enabled
Содержание MM3
Страница 8: ...vi MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 11: ...CHAPTER 1 INTRODUCTION OVERVIEW MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL 1 3 Figure 1 1 Functional block diagram ...
Страница 18: ...1 10 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL TECHNICAL SPECIFICATIONS CHAPTER 1 INTRODUCTION ...
Страница 80: ...4 18 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL CHASSIS MOUNT UNITS CHAPTER 4 SOFTWARE ...
Страница 124: ...5 44 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL S7 TESTING CHAPTER 5 SETPOINTS ...
Страница 198: ...8 54 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL MODBUS MEMORY MAP CHAPTER 8 COMMUNICATIONS ...
Страница 220: ...10 14 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL GE MULTILIN WARRANTY CHAPTER 10 MISCELLANEOUS ...