CHAPTER 8: COMMUNICATIONS
MODBUS MEMORY MAP
MM3 MOTOR MANAGER 3 – INSTRUCTION MANUAL
8–35
Undervoltage/overvoltage protection (read/write setpoints)
44465
4464
1170
Undervoltage alarm level
0 to
691
1
V
F1 *
691 =
0FF
44466
4465
1171
Undervoltage alarm delay
1 to 60
1
s
F1
10
44467
4466
1172
Undervoltage trip level
0 to
691
1
V
F1 *
691 =
0FF
44468
4467
1173
Undervoltage trip delay
1 to 60
1
s
F1
10
44469
4468
1174
Overvoltage alarm level
0 to
691
1
V
F1 *
691 =
0FF
44470
4469
1175
Overvoltage alarm delay
1 to 60
1
s
F1
10
44471
4470
1176
Overvoltage trip level
0 to
691
1
V
F1 *
691 =
0FF
44472
4471
1177
Overvoltage trip delay
1 to 60
1
s
F1
10
44473
4472
1178
...Reserved...
...
...
...
...
...
↓
↓
↓
↓
↓
↓
↓
↓
↓
44480
4479
117F
...Reserved...
...
...
...
...
...
Programmable message (read/write setpoints)
44481
4480
1180
Prog. message characters 1
and 2
32 to
255
1
ASCII
F10
"PR"
44482
4481
1181
Prog. message characters 3
and 4
32 to
255
1
ASCII
F10
"OG"
44483
4482
1182
Prog. message characters 5
and 6
32 to
255
1
ASCII
F10
"RA"
44484
4483
1183
Prog. message characters 7
and 8
32 to
255
1
ASCII
F10
"MM"
44485
4484
1184
Prog. message characters 9
and 10
32 to
255
1
ASCII
F10
"AB"
44486
4485
1185
Prog. message characters
11 and 12
32 to
255
1
ASCII
F10
"LE"
44487
4486
1186
Prog. message characters
13 and 14
32 to
255
1
ASCII
F10
" M"
44488
4487
1187
Prog. message characters
15 and 16
32 to
255
1
ASCII
F10
"ES"
44489
4488
1188
Prog. message characters
17 and 18
32 to
255
1
ASCII
F10
"SA"
44490
4489
1189
Prog. message characters
19 and 20
32 to
255
1
ASCII
F10
"GE"
44491
4490
118A
Prog. message characters
21 and 22
32 to
255
1
ASCII
F10
"SA"
44492
4491
118B
Prog. message characters
23 and 24
32 to
255
1
ASCII
F10
"MP"
44493
4492
118C
Prog. message characters
25 and 26
32 to
255
1
ASCII
F10
"LE"
44494
4493
118D
Prog. message characters
27 and 28
32 to
255
1
ASCII
F10
" T"
44495
4494
118E
Prog. message characters
29 and 30
32 to
255
1
ASCII
F10
"EX"
44496
4495
118F
Prog. message characters
31 and 32
32 to
255
1
ASCII
F10
"T "
Table 8–2: Modbus Memory Map (Sheet 20 of 28)
Modicon
Address
Description
Range
Step
Units Format
Default
dec.
hex
* – Maximum setpoint value and 65535 represent OFF; ** – 1/phase current scale factor
×
A; *** – 101
represents unlimited;
† – Minimum setpoint value represents OFF; ~ – 0.1
×
A when high resolution mode is disabled;
0.01
×
A when enabled
Содержание MM3
Страница 8: ...vi MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 11: ...CHAPTER 1 INTRODUCTION OVERVIEW MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL 1 3 Figure 1 1 Functional block diagram ...
Страница 18: ...1 10 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL TECHNICAL SPECIFICATIONS CHAPTER 1 INTRODUCTION ...
Страница 80: ...4 18 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL CHASSIS MOUNT UNITS CHAPTER 4 SOFTWARE ...
Страница 124: ...5 44 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL S7 TESTING CHAPTER 5 SETPOINTS ...
Страница 198: ...8 54 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL MODBUS MEMORY MAP CHAPTER 8 COMMUNICATIONS ...
Страница 220: ...10 14 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL GE MULTILIN WARRANTY CHAPTER 10 MISCELLANEOUS ...