8–14
MM3 MOTOR MANAGER 3 – INSTRUCTION MANUAL
APPLICATIONS
CHAPTER 8: COMMUNICATIONS
Z
In the “MEMORY MAP INSERTION (WRITE DATA)” section, enter the
first address “1280” into the
Address
box to indicate user-
definable register index 0000.
Z
Enter “0x0031” in the
Values
box to indicate the
PHASE A CURRENT
value. Be sure to enter the 0x prefix to indicate a hex address.
Z
Repeat the above steps for the DRIVE STATUS value.
Z
Press OK.
It is now possible to read these two data registers with one read from addresses 0100h to
0101h. Address 0100h will contain the
PHASE A CURRENT
value and address 0101h will
contain the
DRIVE STATUS
value.
Figure 8-1: Configuring the User-definable Memory Map
Default user map values have been configured. However, the user definable memory map
remains fully customizable. The defaults are separated into three sections: regular polling
data items, data that is read when a trip, stop or alarm occurs, and data that can be
monitored as time permits.
Table 8–1: MM3 Motor Manager 3 Memory Map User Definable Outputs (Sheet 1 of 2)
Modicon
Address
Description
Units
Format Default
Dec
Hex
Regular polling data items
30021
20
0014
General alarm active status flags 1
--
F104
100
30022
21
0015
General alarm active status flags 2
--
F105
101
30023
22
0016
Interlock alarm active status flags
--
F106
102
30027
26
001A
Interlock start block status flags
--
F106
103
30028
27
001B
Trip active status flags 1
--
F107
104
30029
28
001C
Trip active status flags 2
--
F108
105
30035
34
0022
Command mode
--
F6
106
30036
35
0023
Drive status
--
F7
107
Содержание MM3
Страница 8: ...vi MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 11: ...CHAPTER 1 INTRODUCTION OVERVIEW MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL 1 3 Figure 1 1 Functional block diagram ...
Страница 18: ...1 10 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL TECHNICAL SPECIFICATIONS CHAPTER 1 INTRODUCTION ...
Страница 80: ...4 18 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL CHASSIS MOUNT UNITS CHAPTER 4 SOFTWARE ...
Страница 124: ...5 44 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL S7 TESTING CHAPTER 5 SETPOINTS ...
Страница 198: ...8 54 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL MODBUS MEMORY MAP CHAPTER 8 COMMUNICATIONS ...
Страница 220: ...10 14 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL GE MULTILIN WARRANTY CHAPTER 10 MISCELLANEOUS ...