CHAPTER 5: SETPOINTS
S2 PROTECTION
MM3 MOTOR MANAGER 3 – INSTRUCTION MANUAL
5–21
5.3.5
Under/
Overvoltage
Protection
PATH: S2 PROTECTION
ÖØ
UNDER/OVERVOLTAGE PROTECTION
The undervoltage and overvoltage settings are available only if the
VT PRIMARY VOLTAGE
setting is not “OFF”. These setpoints are programmed as follows:
•
UNDERVOLTAGE ALARM LEVEL
: This feature functions the same as the undervoltage
trip feature but produces an alarm indication instead of a trip.
•
UNDERVOLTAGE ALARM DELAY
: Enter the delay for activation of the undervoltage
alarm.
•
UNDERVOLTAGE TRIP LEVEL
: If the voltage remains below this value while the motor
is running for the time specified in the
UNDERVOLTAGE TRIP DELAY
, the MM3 Motor
Manager 3 will trip. Set this value to “OFF” if no undervoltage trip is required.
•
UNDERVOLTAGE TRIP DELAY
: Set the
UNDERVOLTAGE TRIP DELAY
long enough to
prevent nuisance trips from momentary voltage dips when the undervoltage trip
feature is used.
•
OVERVOLTAGE ALARM LEVEL
: This feature functions the same as the overvoltage trip
feature but produces an alarm indication instead of a trip.
•
OVERVOLTAGE ALARM DELAY
: Enter the delay for activation of the overvoltage alarm.
•
OVERVOLTAGE TRIP LEVEL
: If the voltage remains above this value while the motor is
running for the time specified in the
OVERVOLTAGE TRIP DELAY
, the MM3 Motor
Manager 3 will trip. Set this value to “OFF” if no overvoltage trip is required.
•
OVERVOLTAGE TRIP DELAY
: Program this setpoint large enough to prevent nuisance
trips from momentary voltage dips when the undervoltage trip feature is used.
] UNDER/OVERVOLTAGE
] PROTECTION
UNDERVOLTAGE ALARM
LEVEL:
OFF V
Range: 0 to 690 V or OFF in steps of 1
UNDERVOLTAGE ALARM
DELAY: 10 s
Range: 1 to 60 s in steps of 1
UNDERVOLTAGE TRIP
LEVEL:
OFF V
Range: 0 to 690 V or OFF in steps of 1
UNDERVOLTAGE TRIP
DELAY: 10 s
Range: 1 to 60 s in steps of 1
OVERVOLTAGE ALARM
LEVEL:
OFF V
Range: 0 to 690 V or OFF in steps of 1
OVERVOLTAGE ALARM
DELAY:
10 s
Range: 1 to 60 s in steps of 1
OVERVOLTAGE TRIP
LEVEL:
OFF V
Range: 0 to 690 V or OFF in steps of 1
OVERVOLTAGE TRIP
DELAY:
10 s
Range: 1 to 60 s in steps of 1
Содержание MM3
Страница 8: ...vi MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 11: ...CHAPTER 1 INTRODUCTION OVERVIEW MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL 1 3 Figure 1 1 Functional block diagram ...
Страница 18: ...1 10 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL TECHNICAL SPECIFICATIONS CHAPTER 1 INTRODUCTION ...
Страница 80: ...4 18 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL CHASSIS MOUNT UNITS CHAPTER 4 SOFTWARE ...
Страница 124: ...5 44 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL S7 TESTING CHAPTER 5 SETPOINTS ...
Страница 198: ...8 54 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL MODBUS MEMORY MAP CHAPTER 8 COMMUNICATIONS ...
Страница 220: ...10 14 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL GE MULTILIN WARRANTY CHAPTER 10 MISCELLANEOUS ...