EntelliGuard L
TRIP UNIT
TR
OUBLE
2
.8
2-27
2.8 TROUBLESHOOTING
Table 3.1 reviews common problems, their possible cause(s) and solution(s). If problems persist please contact our After Sales Service.
Troubleshooting Guide Trip Unit
Possible Cause
Solution
------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
The trip unit display is blank.
Ex24 VDC is absent.
-- SOLUTION -->
At least 20% of the current sensor rating, (xCT) must be flowing through the breaker to activate the display.
The trip unit display E03.
------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
Memory failure.
-- SOLUTION -->
Return the unit to GE.
The trip unit display E06.
------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
Internal failure.
-- SOLUTION -->
Return the unit to GE.
2.8 Resolução de problemas
Tabela rever problemas comuns, as suas possíveis causas e soluções. Se o problema persiste por favor contacte o nosso departamento de Pós Venda.
Guia de solução de problemas da Unidade de Disparo Possíveis Causas Soluções
------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
A tela da unidade de disparo está em branco.
--- Os +24 VCC não estão ligados.
--
Solução -->
--- Ao menos 20% de corrente nominal do sensor, (xTC) deve fluir pelo sensor de modo a alimentar à unidade de disparo.
------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
A tela da unidade de disparo mostra E03
--- Falha de Memória.
--- Devolva a unidade à GE.
------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
A tela da unidade de disparo mostra E06
--- Falha interna.
--- Devolva a unidade à GE.
2.8
USUWANIE USTEREK
Tabela
3.1
zawiera opis najczęściej występujących problemów, ich możliwe przyczyny i sposoby rozwiązania. Jeśli proponowane metody nie przyniosą skutku - prosimy o kontakt
z naszym Działem Serwisu.
Usterki wyzwalacza nadprądowego
--------------------------------------------------------------------
Wyświetlacz wyzwalacza jest wygaszony.
-----------------
-
--------------------------------------------------
Wyzwalacz nadprądowy wyświetla E03.
--------------------------------------------------------------------
Wyzwalacz nadprądowy wyświetla E06.
Możliwe przyczyny
----------------------------------------------------------------------
Brak zas24 V DC.
-
----------------------------------------------------------------------
Uszkodzona pamięć.
----------------------------------------------------------------------
Błąd wewnętrzny
Rozwiązanie
--------------------------------------------------------------------------------
Aktywacja wyświetlacza wymaga przepływu prądu o wartości
przynajmniej 20% prądu znamionowego przekładnika (xCT).
--------------------------------------------------------------------------------
Przekazać wyzwalacz do GE.
--------------------------------------------------------------------------------
Przekazać wyzwalacz do GE.
Table:
Troubleshooting Guide Breaker
Possible Cause
Solution
------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
Breaker won’t close.
-- Breaker is between CONNECTED, TEST and DISCONNECTED positions.
-- Trip Unit has not been reset.
-- Undervoltage Release is installed but not energized.
-- Interlocks installed.
-- Racking handle inserted.
-- SOLUTION -->
-- Rack circuit breaker to CONNECTED, TEST or DISCONNECTED remove racking handle and close circuit breaker.
-- Push orange button on Trip Unit and close circuit breaker.
-- Energize Undervoltage Release and close circuit breaker.
-- Remove interlocks.
-- Remove handle and close circuit breaker.
-- Check operational diagram (chapter 1.4) and trip the relevant circuit breaker.
Breaker closes then opens instantaneously.
-------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
-- Trip Unit settings are incorrect.
-- Remote Rogowski coil is incorrectly installed.
-- SOLUTION -->
-- Ensure the protection limits setting matches system loads. Ensure inputs are set to normally closed trip without a signal applied.
-- Re-position Coil.
Motor won’t charge.
-----------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
-- Ensure Motor Actuator is installed.
-- SOLUTION -->
-- Install Motor Actuator.
DC closing coil or Undervoltage Release won’t operate.
-----------------------------------------------------------------------------------------------------------------------------------------------------------------------------
-- Ensure the correct polarity of the connection to the secondary isolating contacts.
-- SOLUTION -->
-- Refer to wiring schematic (see Section 1.3).
Circuit breaker won’t rack into cassette.
-----------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
-- Ensure breaker is pushed fully from the maintenance position to DISCONNECTED.
-- Racking drive not in DISCONNECTED position.
-- SOLUTION -->
-- Push breaker into DISCONNECTED position.
-- Ensure racking drive is in DISCONNECTED position.
Cannot insert racking handle.
------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
-- Shutter padlocks are installed.
-- Key locks are installed.
-- SOLUTION -->
-- Remove locks.
Circuit breaker will not go into the DISCONNECTED position.
-----------------------------------------------------------------------------------------------------------------------------------------------------------------------
-- Mis insertion feature is incorrectly set.
-- Circuit breaker is incorrect for given cassette.
-- SOLUTION -->
-- Reset Mis insertion feature.
-- Ensure circuit breaker and cassette go together.
Trip Unit healthy indicator not working. (Fig 2.1)
--------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
-- Ensure Trip Unit, if installed, is energized.
-- Insufficient primary current to power the unit.
-- SOLUTION -->
-- Install Trip Unit, if not installed.
-- Trip Unit will power with 40% In single phase, and 20% In 3 phase current.