LINE DISTANCE PROTECTION SYSTEM – COMMUNICATIONS GUIDE
DNP DEVICE PROFILE
CHAPTER 3: DNP COMMUNICATION
•
Qualifier codes for requests, object 32, variation 0:
–
06 (no range, or all)
–
07, 08 (limited quantity)
There are no codes used for responses.
Object 32, variation 1: 32-bit analog input change events without time
Object 32, variation 2: 16-bit analog input change events without time
Object 32, variation 3: 32-bit analog input change events with time
Object 32, variation 4: 16-bit analog input change events with time
Object 32, variation 5: short floating point analog input change events without time
Object 32, variation 7: short floating point analog input change events with time
The following codes are used for requests.
•
Function codes for requests, object 32, variations 1, 2, 3, 4, 5, and 7:
–
1 (read)
•
Qualifier codes for requests, object 32, variations 1, 2, 3, 4, 5, and 7:
–
06 (no range, or all)
–
07, 08 (limited quantity)
The following codes are used for responses.
•
Function codes for responses, object 32, variations 1, 2, 3, 4, 5, and 7:
–
129 (response)
–
130 (unsolicited response)
•
Qualifier codes for responses, object 32, variations 1, 2, 3, 4, 5, and 7:
–
17, 28 (index)
Object 34 (analog deadbands)
Object 34, variation 0: analog input reporting deadband
Variation 0 is used to request the default variation. The following codes are used for
requests.
•
Function codes for requests, object 34, variation 0:
–
1 (read)
•
Qualifier codes for requests, object 34, variation 0:
–
00, 01 (start-stop)
–
06 (no range, or all)
–
07, 08 (limited quantity)
–
17, 28 (index)
There are no codes used for responses.
Object 34, variation 1: 16-bit analog input reporting deadband
Object 34, variation 2: 32-bit analog input reporting deadband
Object 34, variation 3: short floating point analog input reporting deadband
The following codes are used for requests.
•
Function codes for requests, object 34, variations 1 and 2:
–
1 (read)
–
2 (write)
•
Function codes for requests, object 34, variation 3:
–
1 (read)
•
Qualifier codes for requests, object 34, variations 1, 2, and 3:
–
00, 01 (start-stop)