102
D90
PLUS
LINE DISTANCE PROTECTION SYSTEM – COMMUNICATIONS GUIDE
MODBUS MEMORY MAP
CHAPTER 2: MODBUS COMMUNICATION
7F20
...Repeated for Neutral Overvoltage 3
Auxiliary Overvoltage (Read/Write Grouped Setting) (3 Modules)
7F30
Auxiliary Overvoltage 1 Function
0 to 1
---
1
F102
0 (Disabled)
7F31
Auxiliary Overvoltage 1 Signal Source
0 to 5
---
1
F167
0 (SRC 1)
7F32
Auxiliary Overvoltage 1 Pickup
0 to 1.1
pu
0.001
F001
300
7F33
Auxiliary Overvoltage 1 Pickup Delay
0 to 600
s
0.01
F001
100
7F34
Auxiliary Overvoltage 1 Reset Delay
0 to 600
s
0.01
F001
100
7F35
Auxiliary Overvoltage 1 Block
0 to 65535
---
1
F300
0
7F37
Auxiliary Overvoltage 1 Events
0 to 1
---
1
F102
0 (Disabled)
7F38
Auxiliary Overvoltage 1 Reserved (8 items)
0 to 65535
---
1
F001
0
7F40
...Repeated for Auxiliary Overvoltage 2
7F50
...Repeated for Auxiliary Overvoltage 3
Auxiliary Undervoltage (Read/Write Grouped Setting) (3 Modules)
7F60
Auxiliary Undervoltage 1 Function
0 to 1
---
1
F102
0 (Disabled)
7F61
Auxiliary Undervoltage 1 Signal Source
0 to 5
---
1
F167
0 (SRC 1)
7F62
Auxiliary Undervoltage 1 Pickup
0 to 1.1
pu
0.001
F001
700
7F63
Auxiliary Undervoltage 1 Delay
0 to 600
s
0.01
F001
100
7F64
Auxiliary Undervoltage 1 Curve
0 to 1
---
1
F111
0 (Definite
Time)
7F65
Auxiliary Undervoltage 1 Minimum Voltage
0 to 3
pu
0.001
F001
100
7F66
Auxiliary Undervoltage 1 Block
0 to 65535
---
1
F300
0
7F68
Auxiliary Undervoltage 1 Events
0 to 1
---
1
F102
0 (Disabled)
7F69
Auxiliary Undervoltage 1 Reserved (7 items)
0 to 65535
---
1
F001
0
7F70
...Repeated for Auxiliary Undervoltage 2
7F80
...Repeated for Auxiliary Undervoltage 3
Frequency Actual Values (Read Only)
8000
Tracking Frequency
2 to 90
Hz
0.01
F001
0
Annunciator (Read/Write Setting)
8411
Annunciator Alarm Input (288 items)
0 to 65535
---
1
F300
0
IEC 61850 Logical Node Name Prefixes (Read/Write Setting)
8600
IEC 61850 GGIO LN Prefix (6 items)
0 to 65534
---
1
F206
(none)
Automation Virtual Input Settings (Read/Write Setting) (128 Modules)
92E0
Automation Virtual Input 1 Name
---
---
---
F205
"Aut VI 1 "
92E6
Automation Virtual Input 1 Function
0 to 1
---
1
F102
0 (Disabled)
92E7
Automation Virtual Input 1 Programmed Type
0 to 1
---
1
F127
0 (Latched)
92E8
Automation Virtual Input 1 Events
0 to 1
---
1
F102
0 (Disabled)
92E9
...Repeated for Automation Virtual Input 2
92F2
...Repeated for Automation Virtual Input 3
92FB
...Repeated for Automation Virtual Input 4
9304
...Repeated for Automation Virtual Input 5
930D
...Repeated for Automation Virtual Input 6
9316
...Repeated for Automation Virtual Input 7
931F
...Repeated for Automation Virtual Input 8
9328
...Repeated for Automation Virtual Input 9
9331
...Repeated for Automation Virtual Input 10
933A
...Repeated for Automation Virtual Input 11
9343
...Repeated for Automation Virtual Input 12
Address Description
Range
Units
Step
Format Default