CHAPTER 2: MODBUS COMMUNICATION
MODBUS MEMORY MAP
D90
PLUS
LINE DISTANCE PROTECTION SYSTEM – COMMUNICATIONS GUIDE
55
Frequency Metering Actual Values (Read Only) (6 Modules)
1D80
Source 1 Frequency
2 to 90
Hz
0.001
F003
0
1D82
Source 2 Frequency
2 to 90
Hz
0.001
F003
0
1D84
Source 3 Frequency
2 to 90
Hz
0.001
F003
0
1D86
Source 4 Frequency
2 to 90
Hz
0.001
F003
0
1D88
Source 5 Frequency
2 to 90
Hz
0.001
F003
0
1D8A
Source 6 Frequency
2 to 90
Hz
0.001
F003
0
Energy Metering CommandS (Read/Write Command)
21A0
Energy Clear Command
0 to 1
---
1
F126
0 (No)
Breaker Flashover (Read/Write Setting) (2 Modules)
21A6
Breaker 1 Flashover Function
0 to 1
---
1
F102
0 (Disabled)
21A7
Breaker 1 Flashover Side 1 Source
0 to 5
---
1
F167
0 (SRC 1)
21A8
Breaker 1 Flashover Side 2 Source
0 to 6
---
1
F211
0 (None)
21A9
Breaker 1 Flashover Status Closed A
0 to 65535
---
1
F300
0
21AA
Breaker 1 Flashover Status Closed B
0 to 65535
---
1
F300
0
21AB
Breaker 1 Flashover Status Closed C
0 to 65535
---
1
F300
0
21AC
Breaker 1 Flashover Voltage Pickup Level
0 to 1.5
pu
0.001
F001
850
21AD
Breaker 1 Flashover Voltage Difference Pickup Level 0 to 100000
V
1
F060
1000
21AF
Breaker 1 Flashover Current Pickup Level
0 to 1.5
pu
0.001
F001
600
21B0
Breaker 1 Flashover Pickup Delay
0 to 65.535
s
0.001
F001
100
21B1
Breaker 1 Flashover Supervision Phase A
0 to 0 to 65535
---
1
F300
0
21B2
Breaker 1 Flashover Supervision Phase B
0 to 0 to 65535
---
1
F300
0
21B3
Breaker 1 Flashover Supervision Phase C
0 to 0 to 65535
---
1
F300
0
21B4
Breaker 1 Flashover Block
0 to 0 to 65535
---
1
F300
0
21B5
Breaker 1 Flashover Events
0 to 1
---
1
F102
0 (Disabled)
21B6
Reserved (5 items)
---
---
---
F001
0
21BB
...Repeated for Breaker 2 Flashover
Breaker Arcing Current Actual Values (Read Only) (3 Modules)
21E0
Breaker 1 Arcing Accumulated Arcing Current Phase
A
0 to 99999999
kA
2
-cyc 1
F060
0
21E2
Breaker 1 Arcing Accumulated Arcing Current Phase
B
0 to 99999999
kA
2
-cyc 1
F060
0
21E4
Breaker 1 Arcing Accumulated Arcing Current Phase
C
0 to 99999999
kA
2
-cyc 1
F060
0
21E6
Breaker 1 Arcing Clearing Time Phase A
0 to 65535
ms
1
F001
0
21E7
Breaker 1 Arcing Clearing Time Phase B
0 to 65535
ms
1
F001
0
21E8
Breaker 1 Arcing Clearing Time Phase C
0 to 65535
ms
1
F001
0
21E9
Breaker 1 Arcing Clearing Time
0 to 65535
ms
1
F001
0
21EA
Breaker 1 Arcing Current Phase A
0 to 99999999
kA
1
F060
0
21EC
Breaker 1 Arcing Current Phase B
0 to 99999999
kA
1
F060
0
21EE
Breaker 1 Arcing Current Phase C
0 to 99999999
kA
1
F060
0
21F0
Breaker 1 Arcing Maximum Arcing Current Phase A
0 to 99999999
kA
1
F060
0
21F2
Breaker 1 Arcing Maximum Arcing Current Phase B
0 to 99999999
kA
1
F060
0
21F4
Breaker 1 Arcing Maximum Arcing Current Phase C
0 to 99999999
kA
1
F060
0
21F6
Breaker 2 Arcing Accumulated Arcing Current Phase
A
0 to 99999999
kA
2
-cyc 1
F060
0
21F8
Breaker 2 Arcing Accumulated Arcing Current Phase
B
0 to 99999999
kA
2
-cyc 1
F060
0
Address Description
Range
Units
Step
Format Default