96
D90
PLUS
LINE DISTANCE PROTECTION SYSTEM – COMMUNICATIONS GUIDE
MODBUS MEMORY MAP
CHAPTER 2: MODBUS COMMUNICATION
7145
Ground Distance Zone 1 Non-Homogeneous Angle
-40 to 40
degrees 0.1
F002
0
7146
Ground Distance Zone 1 POL Current
0 to 1
---
1
F521
0 (Zero-seq)
7147
Ground Distance Zone 1 Reverse Reach
0.02 to 500
ohms
0.01
F001
200
7148
Ground Distance Zone 1 Reverse Reach RCA
30 to 90
degrees 1
F001
85
7149
Reserved (7 items)
0 to 65535
---
1
F001
0
7150
...Repeated for Ground Distance Zone 2
7170
...Repeated for Ground Distance Zone 3
7190
...Repeated for Ground Distance Zone 4
71B0
...Repeated for Ground Distance Zone 5
Line Pickup (Read/Write Grouped Setting)
71F0
Line Pickup Function
0 to 1
---
1
F102
0 (Disabled)
71F1
Line Pickup Signal Source
0 to 5
---
1
F167
0 (SRC 1)
71F2
Line Pickup Phase IOC Pickup
0 to 30
pu
0.001
F001
1000
71F3
Line Pickup UV Pickup
0 to 3
pu
0.001
F001
700
71F4
Line End Open Pickup Delay
0 to 65.535
s
0.001
F001
150
71F5
Line End Open Reset Delay
0 to 65.535
s
0.001
F001
90
71F6
Line Pickup OV Pickup Delay
0 to 65.535
s
0.001
F001
40
71F7
Autoreclose Coordination Pickup Delay
0 to 65.535
s
0.001
F001
45
71F8
Autoreclose Coordination Reset Delay
0 to 65.535
s
0.001
F001
5
71F9
Autoreclose Coordination Bypass
0 to 1
---
1
F102
1 (Enabled)
71FA
Line Pickup Block
0 to 65535
---
1
F300
0
71FC
Line Pickup Events
0 to 1
---
1
F102
0 (Disabled)
71FD
Terminal Open
0 to 65535
---
1
F300
0
71FE
Autoreclose Accelerate
0 to 65535
---
1
F300
0
71FF
Line Pickup Distance Trip
0 to 1
---
1
F102
1 (Enabled)
Breaker Failure (Read/Write Grouped Setting) (2 Modules)
7200
Breaker Failure 1 Function
0 to 1
---
1
F102
0 (Disabled)
7201
Breaker Failure 1 Mode
0 to 1
---
1
F157
0 (3-Pole)
7208
Breaker Failure 1 Source
0 to 5
---
1
F167
0 (SRC 1)
7209
Breaker Failure 1 Amp Supervision
0 to 1
---
1
F126
1 (Yes)
720A
Breaker Failure 1 Use Seal-In
0 to 1
---
1
F126
1 (Yes)
720B
Breaker Failure 1 Three Pole Initiate
0 to 65535
---
1
F300
0
720C
Breaker Failure 1 Block
0 to 65535
---
1
F300
0
720D
Breaker Failure 1 Phase Amp Supv Pickup
0.001 to 30
pu
0.001
F001
1050
720E
Breaker Failure 1 Neutral Amp Supv Pickup
0.001 to 30
pu
0.001
F001
1050
720F
Breaker Failure 1 Use Timer 1
0 to 1
---
1
F126
1 (Yes)
7210
Breaker Failure 1 Timer 1 Pickup
0 to 65.535
s
0.001
F001
0
7211
Breaker Failure 1 Use Timer 2
0 to 1
---
1
F126
1 (Yes)
7212
Breaker Failure 1 Timer 2 Pickup
0 to 65.535
s
0.001
F001
0
7213
Breaker Failure 1 Use Timer 3
0 to 1
---
1
F126
1 (Yes)
7214
Breaker Failure 1 Timer 3 Pickup
0 to 65.535
s
0.001
F001
0
7215
Breaker Failure 1 Breaker Status 1 Phase A/3P
0 to 65535
---
1
F300
0
7216
Breaker Failure 1 Breaker Status 2 Phase A/3P
0 to 65535
---
1
F300
0
7217
Breaker Failure 1 Breaker Test On
0 to 65535
---
1
F300
0
7218
Breaker Failure 1 Phase Amp Hiset Pickup
0.001 to 30
pu
0.001
F001
1050
7219
Breaker Failure 1 Neutral Amp Hiset Pickup
0.001 to 30
pu
0.001
F001
1050
721A
Breaker Failure 1 Phase Amp Loset Pickup
0.001 to 30
pu
0.001
F001
1050
Address Description
Range
Units
Step
Format Default