112
D90
PLUS
LINE DISTANCE PROTECTION SYSTEM – COMMUNICATIONS GUIDE
MODBUS MEMORY MAP
CHAPTER 2: MODBUS COMMUNICATION
A2E0
FlexElement 9 Actual
-2147483.647 to
2147483.647
---
0.001
F004
0
A2E2
FlexElement 10 Actual
-2147483.647 to
2147483.647
---
0.001
F004
0
A2E4
FlexElement 11 Actual
-2147483.647 to
2147483.647
---
0.001
F004
0
A2E6
FlexElement12 Actual
-2147483.647 to
2147483.647
---
0.001
F004
0
A2E8
FlexElement 13 Actual
-2147483.647 to
2147483.647
---
0.001
F004
0
A2EA
FlexElement 14 Actual
-2147483.647 to
2147483.647
---
0.001
F004
0
A2EC
FlexElement 15 Actual
-2147483.647 to
2147483.647
---
0.001
F004
0
A2EE
FlexElement 16 Actual
-2147483.647 to
2147483.647
---
0.001
F004
0
Fault Report Settings (Read/Write Setting) (5 Modules)
A350
Fault Report 1 Source
0 to 5
---
1
F167
0 (SRC 1)
A351
Fault Report 1 Trigger
0 to 65535
---
1
F300
0
A352
Fault Report 1 Z1 Magnitude
0.01 to 250
ohms
0.01
F001
300
A353
Fault Report 1 Z1 Angle
25 to 90
degrees 1
F001
75
A354
Fault Report 1 Z0 Magnitude
0.01 to 650
ohms
0.01
F001
900
A355
Fault Report 1 Z0 Angle
25 to 90
degrees 1
F001
75
A356
Fault Report 1 Line Length Units
0 to 1
---
1
F147
0 (km)
A357
Fault Report 1 Line Length
0 to 2000
0.1
F001
1000
A358
Fault Report 1 VT Substitution
0 to 2
---
1
F270
0 (None)
A359
Fault Report 1 System Z0 Magnitude
0.01 to 650.00
ohms
0.01
F001
200
A35A
Fault Report 1 System Z0 Angle
25 to 90
degrees 1
F001
75
A35B
...Repeated for Fault Report 2
A366
...Repeated for Fault Report 3
A371
...Repeated for Fault Report 4
A37C
...Repeated for Fault Report 5
VT Fuse Failure Settings (Read/Write Setting) (6 Modules)
A3F0
VT Fuse Failure 1 Function
0 to 1
---
1
F102
0 (Disabled)
A3F1
...Repeated for VT Fuse Failure 2
A3F2
...Repeated for VT Fuse Failure 3
A3F3
...Repeated for VT Fuse Failure 4
A3F4
...Repeated for VT Fuse Failure 5
A3F5
...Repeated for VT Fuse Failure 6
Selector Switch Actual Values (Read Only) (10 Modules)
A400
Selector 1 Position
1 to 7
---
1
F001
0
A401
Selector 2 Position
1 to 7
---
1
F001
0
A402
Selector 3 Position
1 to 7
---
1
F001
0
A403
Selector 4 Position
1 to 7
---
1
F001
0
A404
Selector 5 Position
1 to 7
---
1
F001
0
A405
Selector 6 Position
1 to 7
---
1
F001
0
A406
Selector 7 Position
1 to 7
---
1
F001
0
A407
Selector 8 Position
1 to 7
---
1
F001
0
A408
Selector 9 Position
1 to 7
---
1
F001
0
Address Description
Range
Units
Step
Format Default