154
D90
PLUS
LINE DISTANCE PROTECTION SYSTEM – COMMUNICATIONS GUIDE
MODBUS MEMORY MAP
CHAPTER 2: MODBUS COMMUNICATION
E640
PMU Auxiliary Voltage Test Magnitude
0 to 700
kV
0.01
F003
50000
E642
PMU Auxiliary Voltage Test Angle
-180 to 180
°
0.05
F002
0
E643
PMU Phase A Current Test Magnitude
0 to 9.999
kA
0.001
F004
1000
E645
PMU Phase A Current Test Angle
-180 to 180
°
0.05
F002
-1000
E646
PMU Phase B Current Test Magnitude
0 to 9.999
kA
0.001
F004
1000
E648
PMU Phase B Current Test Angle
-180 to 180
°
0.05
F002
-13000
E649
PMU Phase C Current Test Magnitude
0 to 9.999
kA
0.001
F003
1000
E64B
PMU Phase C Current Test Angle
-180 to 180
°
0.05
F002
11000
E64C
PMU Ground Current Test Magnitude
0 to 9.999
kA
0.001
F004
0
E64E
PMU Ground Current Test Angle
-180 to 180
°
0.05
F002
0
E64F
PMU Test Frequency
20 to 70
Hz
0.001
F003
60000
E651
PMU Test df/dt
-10 to 10
Hz/s
0.01
F002
0
Phasor Measurement Unit Triggering (Read/Write Setting)
E652
PMU User Trigger
0 to 65535
---
1
F300
0
Phasor Measurement Unit Voltage Trigger (Read/Write Setting)
E653
PMU Voltage Trigger Function
0 to 1
---
1
F102
0 (Disabled)
E654
PMU Voltage Trigger Low Volt
0.25 to 1.25
pu
0.001
F001
800
E655
PMU Voltage Trigger High Volt
0.75 to 1.75
pu
0.001
F001
1200
E656
PMU Voltage Trigger Pkp Time
0 to 600
s
0.01
F001
10
E657
PMU Voltage Trigger Dpo Time
0 to 600
s
0.01
F001
100
E658
PMU Voltage Trigger Block
0 to 65535
---
1
F300
0
E65C
PMU Voltage Trigger Events
0 to 1
---
1
F102
0 (Disabled)
Phasor Measurement Unit RS485 Reporting Configuration (Read/Write Setting)
E65D
Reserved (163 items)
Remote Devices (Read/Write Setting) (32 Modules)
E700
Remote Device 1 ID
---
---
---
F209
"Remote
Device 1"
E721
Remote Device 1 Ethernet APPID
0 to 16383
---
1
F001
0
E722
Remote Device 1 Dataset
0 to 8
---
1
F184
0 (Fixed)
E723
...Repeated for Remote Device 2
E744
...Repeated for Remote Device 2
E745
...Repeated for Remote Device 2
E746
...Repeated for Remote Device 3
E769
...Repeated for Remote Device 4
E78A
...Repeated for Remote Device 4
E7AD
...Repeated for Remote Device 5
E7AE
...Repeated for Remote Device 5
E7AF
...Repeated for Remote Device 6
E7D0
...Repeated for Remote Device 6
E7D1
...Repeated for Remote Device 6
E7D2
...Repeated for Remote Device 7
E7F3
...Repeated for Remote Device 7
Address Description
Range
Units
Step