72
D90
PLUS
LINE DISTANCE PROTECTION SYSTEM – COMMUNICATIONS GUIDE
MODBUS MEMORY MAP
CHAPTER 2: MODBUS COMMUNICATION
3350
Modbus File Transfer Filename 2
---
---
---
F204
(none)
3378
Modbus File Transfer State 2
0 to 7
---
1
F095
0 (IDLE)
3379
Modbus File Transfer Position 2
0 to 4294967295
---
1
F003
0
337B
Modbus File Transfer Block Size 2
0 to 65535
---
1
F001
0
337C
Modbus File Transfer Data 2 (122 items)
0 to 65535
---
1
F001
0
Event Recorder Actual Values (Read Only)
3400
Events Since Last Clear
0 to 4294967295
---
1
F003
0
3402
Number of Available Events
0 to 4294967295
---
1
F003
0
3404
Event Recorder Last Cleared Date
0 to 4294967295
---
1
F050
0
Event Recorder (Read/Write Command)
3406
Event Recorder Clear Command
0 to 1
---
1
F126
0 (No)
Event Recorder Actual Values (Read Only)
3408
Event Recorder Last Time Stamp
0 to 4294967295
---
1
F003
0
Miscellaneous Actual Values (Read Only)
3410
Settings File Last Change Date
0 to 4294967295
---
1
F050
0
3412
CPU Status
0 to 2
---
1
F097
0 (Out of
Service)
Miscellaneous (Read/Write)
3413
Front Panel Status
0 to 65535
---
1
F001
0
Miscellaneous (Read/Write Setting)
3414
Web Server Function
0 to 1
---
1
F102
0 (Disabled)
3415
HTTP IP Port Number
1 to 65535
---
1
F001
80
Disturbance Recorder (Read/Write Setting)
3420
Disturbance Record Function
0 to 1
---
1
F102
1 (Enabled)
3421
Disturbance Record Number of Records
1 to 64
---
1
F001
48
3422
Disturbance Record Trigger Mode
0 to 1
---
1
F118
0 (Automatic
Overwrite)
3423
Disturbance Record Trigger Position
1 to 100
%
1
F001
50
3424
Disturbance Record Analog Channel (64 items)
0 to 4294967295
---
1
F600
0
34A4
Disturbance Record Digital Channel (32 items)
0 to 65535
---
1
F300
0
34C4
Disturbance Record Analog Channel High Trigger (64
items)
0 to 3
---
1
F094
0 (OFF)
3504
Disturbance Record Analog Channel Low Trigger (64
items)
0 to 3
---
1
F094
0 (OFF)
3544
Disturbance Record Digital Channel Trigger (32 items) 0 to 3
---
1
F094
0 (OFF)
3564
Disturbance Record Analog Channel High Pickup (64
items)
0 to 1000000
---
0.1
F003
10000
35E4
Disturbance Record Analog Channel Low Pickup (64
items)
0 to 1000000
---
0.1
F003
10000
3664
Disturbance Record Block Trigger
0 to 65535
---
1
F300
0
3665
Disturbance Record Analog Channel Block Trigger (64
items)
0 to 65535
---
1
F300
0
36A5
Disturbance Record Maximum Retriggers
1 to 4
---
1
F001
2
Disturbance Recorder Commands (Read/Write Command)
36B0
Disturbance Record Force Trigger
0 to 1
---
1
F126
0 (No)
36B1
Disturbance Record Clear Data
0 to 1
---
1
F126
0 (No)
Disturbance Recorder Actual Values (Read Only)
36C0
Disturbance Record Trigger Secs (64 items)
0 to 4294967295
---
0.1
F003
0
3740
Disturbance Record Newest File Number
0 to 65535
---
1
F001
0
Address Description
Range
Units
Step
Format Default