Mains Supply 3 x 525- 690 VAC
AF-650 GP
1250 HP
1350 HP
Heavy Duty/Light Duty*
HD
LD
HD
LD
Typical Shaft output at 550 V [kW]
750
850
850
1000
Typical Shaft output at 575 V [HP]
1050
1150
1150
1350
Typical Shaft output at 690 V [kW]
900
1000
1000
1200
IP21/Nema 1 and IP54/Nema 12 Drive
Types without/with options cabinet
62/ 64
62/ 64
Output current
Continuous
(at 550 V) [A]
988
1108
1108
1317
Intermittent (60 sec overload)
(at 550 V) [A]
1482
1219
1662
1449
Continuous
(at 575/ 690 V) [A]
945
1060
1060
1260
Intermittent (60 sec overload)
(at 575/ 690 V) [A]
1418
1166
1590
1386
Continuous KVA
(at 550 V) [KVA]
941
1056
1056
1255
Continuous KVA
(at 575 V) [KVA]
941
1056
1056
1255
Continuous KVA
(at 690 V) [KVA]
1129
1267
1267
1506
Max. input current
Continuous
(at 550 V ) [A]
962
1079
1079
1282
Continuous
(at 575 V) [A]
920
1032
1032
1227
Continuous
(at 690 V) [A]
920
1032
1032
1227
Max. cable size, motor [mm
2
(AWG
2)
)]
12x150
(12x300 mcm)
Max. cable size,mains F2 [mm
2
(AWG
2)
)]
8x240
(8x500 mcm)
Max. cable size,mains F4 [mm
2
(AWG
2)
)]
8x456
(8x900 mcm)
Max. cable size, loadsharing [mm
2
(AWG
2)
)]
4x120
(4x250 mcm)
Max. cable size, brake [mm
2
(AWG
2)
)
6x185
(6x350 mcm)
Max. external mains fuses [A]
1
1600
2000
Estimated power loss
at 600 V [W]
4)
13755
15592
15107
18281
Estimated power loss
at 690V [W]
4)
14457
16375
15899
19207
F3/F4 Max added losses CB or Disconnect
& Contactor
556
665
634
863
Max panel options losses
400
Weight,
Unit Size IP21, IP 54 [kg]
1246/ 1541
1246/ 1541
Weight, Rectifier Module [kg]
136
136
Weight, Inverter Module [kg]
102
102
Efficiency
4)
0.98
Output frequency
0-500 Hz
Heatsink
overtemp.
trip
85 °C
Power card ambient trip
68 °C
* Heavy Duty = 160% torque during 60 s, Light Duty = 110% torque during 60 s
1) For type of fuse see section
Fuses.
2) American Wire Gauge.
3) Measured using 5 m screened motor cables at rated load and rated frequency.
4) The typical power loss is at nominal load conditions and expected to be /-15% (tolerence relates to variety in voltage and cable conditions).
Values are based on a typical motor efficiency (eff2/eff3 border line). Motors with lower efficiency will also add to the power loss in the frequency converter
and opposite.
If the switching frequency is increased compared to the default setting, the power losses may rise significantly.
Keypad and typical control card power consumptions are included. Further options and customer load may add up to 30W to the losses. (Though typical
only 4W extra for a fully loaded control card, or options for slot A or slot B, each).
Although measurements are made with state of the art equipment, some measurement inaccuracy must be allowed for (+/-5%).
AF-650 GP Design Guide
70
4
Содержание AF-650 GP Series
Страница 5: ...AF 650 GP Design Guide 4 1...
Страница 53: ...AF 650 GP Design Guide 52 4...
Страница 97: ...Please note airflow directions 6 1 5 Mechanical Dimensions AF 650 GP Design Guide 96 6...
Страница 98: ...Please note airflow directions AF 650 GP Design Guide 97 6...
Страница 99: ...Please note airflow directions AF 650 GP Design Guide 98 6...
Страница 100: ...Please note airflow directions AF 650 GP Design Guide 99 6...
Страница 173: ...Max cable length 150 m AF 650 GP Design Guide 172 9...
Страница 179: ...AF 650 GP Design Guide 178 9...