Parameter set-up Torque open loop in Advanced Vector Control mode
Function
Parameter
Setting
Data Value
Basic Settings
Configuration Mode
H-40
Torque Open Loop
[4]
Motor Control Principle
H-41
Advanced Vector
[1]
Torque PI control settings
Torque PI Proportional Gain
PI-12
Default 100 %
Torque PI Integration Time
PI-13
Default 0.02 sec
Reference Handling (Nm) Reference 53; Limit 54
Reference range
F-50
Min - max
[0]
Terminal 53 Low Voltage
AN-10
0V (Default 0.07V)
Terminal 53 High Voltage
AN-11
10V
Terminal 53 Low Ref.
AN-14
0 Nm
Terminal 53 High Ref
AN-15
Max torque on motor shaft
Speed Limit Factor Adjustable on input 54
Terminal 54 Low Voltage
AN-20
0V (default 0.07V)
Terminal 54 High Voltage
AN-21
10 V
Terminal 54 Low Ref
AN-24
0V
Terminal 54 High Ref
AN-25
1500 rpm (adjustable setting)
AF-650 GP Design Guide
166
8