7.7 Additional Connections
7.7.1 DC Bus Connection (only available on frequency converters with factory installed brake chopper)
The DC bus terminal is used for DC back-up, with the intermediate circuit being supplied from an external source.
Terminal numbers used: 88, 89
Please contact GE if you require further information.
7.7.2 Load Sharing(only available on frequency converters with factory installed brake chopper)
Terminal No.
Function
88, 89
Loadsharing
The connection cable must be screened and the max. length from the frequency converter to the DC bar is limited to 25 metres (82 feet).
Load sharing enables linking of the DC intermediate circuits of several frequency converters.
Please note that voltages up to 1099 VDC may occur on the terminals.
Load Sharing calls for extra equipment and safety considerations. For further information, please contact GE.
Please note that mains disconnect may not isolate the frequency converter due to DC link connection
AF-650 GP Design Guide
149
7