10.10 GE Drive Control Profile
10.10.1 Control Word According to Drive Profile (par. O-10
Control Word Profile
= Drive profile)
Bit
Bit value = 0
Bit value = 1
00
Reference value
external selection lsb
01
Reference value
external selection msb
02
DC brake
Ramp
03
Coasting
No coasting
04
Quick stop
Ramp
05
Hold output frequency
use ramp
06
Ramp stop
Start
07
No function
Reset
08
No function
Jog
09
Ramp 1
Ramp 2
10
Data invalid
Data valid
11
No function
Relay 01 active
12
No function
Relay 02 active
13
Parameter set-up
selection lsb
14
Parameter set-up
selection msb
15
No function
Reverse
Explanation of the Control Bits
Bits 00/01
Bits 00 and 01 are used to choose between the four reference values, which are pre-programmed in par. C-05
Multi-step Frequency 1 - 8
according to the following
table:
Programmed ref. value
Par.
Bit 01
Bit 00
1
Par. C-05
Multi-step Frequency 1 - 8
[0] 0
0
2
Par. C-05
Multi-step Frequency 1 - 8
[1] 0
1
3
Par. C-05
Multi-step Frequency 1 - 8
[2] 1
0
4
Par. C-05
Multi-step Frequency 1 - 8
[3] 1
1
NB!
Make a selection in par. O-56
Preset Reference Select
to define how Bit 00/01 gates with the corresponding function on the digital inputs.
Bit 02, DC brake:
Bit 02 = ’0’ leads to DC braking and stop. Set braking current and duration in par. B-01
DC Brake Current
and par. B-02
DC Braking Time
. Bit 02 = ’1’ leads to ramping.
AF-650 GP Design Guide
196
10
Содержание AF-650 GP Series
Страница 5: ...AF 650 GP Design Guide 4 1...
Страница 53: ...AF 650 GP Design Guide 52 4...
Страница 97: ...Please note airflow directions 6 1 5 Mechanical Dimensions AF 650 GP Design Guide 96 6...
Страница 98: ...Please note airflow directions AF 650 GP Design Guide 97 6...
Страница 99: ...Please note airflow directions AF 650 GP Design Guide 98 6...
Страница 100: ...Please note airflow directions AF 650 GP Design Guide 99 6...
Страница 173: ...Max cable length 150 m AF 650 GP Design Guide 172 9...
Страница 179: ...AF 650 GP Design Guide 178 9...