Note: par. F-15
Motor Speed High Limit [Hz]
is a single word, and the parameter
command for write in EEPROM is “E”. Parameter number F-15 is 00F in hex-
adecimal.
The response from the slave to the master will be:
10.5.2 Reading a Parameter Value
Read the value in par. F-07
Accel Time 1
PKE = 1007 Hex - Read parameter value in par. F-07
Accel Time 1
IND = 0000 Hex
PWEHIGH = 0000 Hex
PWELOW = 0000 Hex
If the value in par. F-07
Accel Time 1
is 10 s, the response from the slave to
the master will be:
3E8 Hex corresponds to 1000 decimal. The conversion index for par. F-07
Accel Time 1
is -2, i.e. 0.01.
par. F-07
Accel Time 1
is of the type
Unsigned 32
.
AF-650 GP Design Guide
189
10