7.1.2 Connection to Mains and Earthing
NB!
The plug connector for power is plugable on frequency converters up to 7.5 kW.
1.
Fit the two screws in the de-coupling plate, slide it into place and tighten the screws.
2.
Make sure the frequency converter is properly earthed. Connect to earth connection (terminal 95). Use screw from the accessory bag.
3.
Place plug connector 91(L1), 92(L2), 93(L3) from the accessory bag onto the terminals labelled MAINS at the bottom of the frequency converter.
4.
Attach mains wires to the mains plug connector.
5.
Support the cable with the supporting enclosed brackets.
NB!
Check that mains voltage corresponds to the mains voltage of the name plate.
IT Mains
Do not connect 400 V frequency converters with RFI-filters to mains supplies with a voltage between phase and earth of more than 440 V.
The earth connection cable cross section must be at least 10 mm
2
or 2 x rated mains wires terminated separately according to EN 50178.
The mains connection is fitted to the mains switch if this is included.
AF-650 GP Design Guide
118
7
Содержание AF-650 GP Series
Страница 5: ...AF 650 GP Design Guide 4 1...
Страница 53: ...AF 650 GP Design Guide 52 4...
Страница 97: ...Please note airflow directions 6 1 5 Mechanical Dimensions AF 650 GP Design Guide 96 6...
Страница 98: ...Please note airflow directions AF 650 GP Design Guide 97 6...
Страница 99: ...Please note airflow directions AF 650 GP Design Guide 98 6...
Страница 100: ...Please note airflow directions AF 650 GP Design Guide 99 6...
Страница 173: ...Max cable length 150 m AF 650 GP Design Guide 172 9...
Страница 179: ...AF 650 GP Design Guide 178 9...