9. ACCEPTANCE TESTS
9-6
DTP-B Digital Transformer Protection
GEK-106243E
9.13 INSTANTANEOUS FUNCTION CHECKING
•
Disable the harmonic restraints, and the differential function, and enable the instantaneous function.
•
Set the instantaneous function to 4 times the tap.
•
Apply current to the primary, and check that it trips when the differential current reaches the set value.
Check that it trips with an error margin of less than 5% for different differential currents, and different
instantaneous function settings.