4. FUNCTIONS DESCRIPTION
4-2
DTP-B Digital Transformer Protection
GEK-106243E
There is a test option for the LEDs, lighting them all up when the TARGET RESET button is pressed. When this
button is held down the LED indicators are reset.
The DTP units are supplied from the manufacturer with the following default configuration of the LEDs:
LED No
DESCRIPTION
LED No
DESCRIPTION
1
87 A Trip
9
Temperature Alarm
2
87 B Trip
10
Temperature Trip
3
87 C Trip
11
Out of Service
4
87B A Trip
12
Trip not permitted
5
87B B Trip
13
EEPROM Alarm
6
87B C Trip
14
Date & Time Alarm
7
Buchholz Alarm
15
Internal communication
f il
8
Buchholz Trip
16
Remote mode
4.2.3 SELF-CHECKING FUNCTIONS
As an advantage of its digital technology, the DTP system incorporates self-checking functions, which guarantee
the correct performance of the unit and will block the operation in case of internal errors.
These self monitoring checks are carried out both when the unit is started up and during normal operation. The
checks are carried out on the internal power supply, program memory (ROM), working memory (RAM),
oscillographic memory (RAM) and settings and calibration memory (EEPROM).
In addition there is a hardware test for the LED indicators, which light them all up when the button TARGET
RESET is pressed. If the button is kept pressed down for more than one second the memory for all the indicators
will be reset.
Содержание DTP-B
Страница 23: ...3 OPERATING PRINCIPLES 3 6 DTP B Digital Transformer Protection GEK 106243E ...
Страница 53: ...10 INSTALLATION AND MAINTENANCE 10 2 DTP B Digital Transformer Protection GEK 106243E ...
Страница 66: ...12 FIGURES GEK 106243E DTP Digital Transformer Protection 12 1 12 FIGURES Figure 1 External Connections ...
Страница 67: ...12 FIGURES 12 2 DTP B Digital Transformer Protection GEK 106243E Figure 2 Panel Drilling Dimensions ...
Страница 68: ...12 FIGURES GEK 106243E DTP Digital Transformer Protection 12 3 Figure 3 RS 232 Connection ...
Страница 69: ...12 FIGURES 12 4 DTP B Digital Transformer Protection GEK 106243E Figure 4 Dimensions Diagram ...
Страница 70: ...12 FIGURES GEK 106243E DTP Digital Transformer Protection 12 5 Figure 5 Front View ...
Страница 73: ...12 FIGURES 89 DTP B Digital Transformer Protection GEK 106243E Figure 8 Block Diagram of the Protection ...