9. ACCEPTANCE TESTS
GEK-106243E
DTP Digital Transformer Protection
9-5
9.10 OPERATIONS
9.10.1 TIME SETTING.
Set the date and time, and check that the setting is performed successfully.
9.10.2 COMMUNICATIONS TRIGGER.
Apply a known current by any of the phases, and operate the communications trigger. Verify, retrieving the header
of the last oscillography record by means of the GE-LOCAL software, that the retrieved time coincides with the
correct time.
9.11 PERCENTAGE RESTRAINT CHECKING
•
Disable the harmonic restraints, and enable the differential function.
•
Set sensitivity to 0.3, and percentage restraints to 50%
•
Apply current to the primary and secondary, so that we have a differential current of 0.00, and a through
current of 2.
•
Increase the current in the primary, and check that it trips when the differential current is equal or higher than
0.3 + 2.00 x 0.5 = 1.30
Check that it trips with an error margin of less than 5% for different through currents, and different sensitivity and
percentage restraint settings.
9.12 HARMONIC RESTRAINT CHECKING
•
Enable the harmonic restraints, and the differential function.
•
Set sensitivity to 0.3, percentage restraints to 50%, and harmonic restraints to 20%.
•
Apply current to the primary and secondary, so that we have a differential current of 0.00, and a through
current of 2.
•
Apply to the primary a second harmonic current of 0.5 Amps, besides the current it already had.
•
Increase the current in the primary, and check that it trips when the differential current is equal or higher than
0.3 + 2.00 x 0.5 + 0.5 / 0.2 = 3.8
Check that it trips with an error margin of less than 5% for different through currents, and different sensitivity and
percentage restraint settings.
Содержание DTP-B
Страница 23: ...3 OPERATING PRINCIPLES 3 6 DTP B Digital Transformer Protection GEK 106243E ...
Страница 53: ...10 INSTALLATION AND MAINTENANCE 10 2 DTP B Digital Transformer Protection GEK 106243E ...
Страница 66: ...12 FIGURES GEK 106243E DTP Digital Transformer Protection 12 1 12 FIGURES Figure 1 External Connections ...
Страница 67: ...12 FIGURES 12 2 DTP B Digital Transformer Protection GEK 106243E Figure 2 Panel Drilling Dimensions ...
Страница 68: ...12 FIGURES GEK 106243E DTP Digital Transformer Protection 12 3 Figure 3 RS 232 Connection ...
Страница 69: ...12 FIGURES 12 4 DTP B Digital Transformer Protection GEK 106243E Figure 4 Dimensions Diagram ...
Страница 70: ...12 FIGURES GEK 106243E DTP Digital Transformer Protection 12 5 Figure 5 Front View ...
Страница 73: ...12 FIGURES 89 DTP B Digital Transformer Protection GEK 106243E Figure 8 Block Diagram of the Protection ...