9. ACCEPTANCE TESTS
9-2
DTP-B Digital Transformer Protection
GEK-106243E
9.4 POWER SUPPLY
For safety reasons, P12 terminal must be grounded during
functional tests.
The relay is connected to a power supply, at minimum and maximum rated voltage. For each of these voltages,
check that the ALARM relay is open when the unit is powered, and closed when it is not powered.
Generate an 87B trip by the three phases, and activate the Buchholz Alarm, and Overtemperature Alarm inputs.
When the relay is tripped, measure its DC power consumption, and check that it communicates correctly.
The typical test voltages and burdens are as follows:
Model A
Model H
Vdc Voltage
Typical consumption (mA)
Vdc Voltage
Typical consumption (mA)
38
550
80
550
48
227
250
225
58
205
300
205
9.5 MEASUREMENT CHECK
Check that the unit measures correctly applying current by one of the phases to the primary and secondary
windings.
Please take into account that the differential and through currents are given in times the tap, and the tap is
obtained from:
Tap = Winding tap setting x In.
For example, if all the winding taps are set to 0.5, and the rated current is 5Amp, the tap is 0.5x5= 2.5 Amp. If then
we apply 2.5 Amp, only to the first winding, the relay must measure a differential current of 1.00 and a through
current of 0.00. If the current is applied also to the second winding, it must give the following values:
If the unit sees both currents in phase Id = 2.00 and It = 0.00
If the unit sees both currents in counterphase Id = 0.00 and It = 1.00
Repeat the test with different values, and by the three phases, and check that the obtained values do not differ
from the expected in more than a 5%.
Содержание DTP-B
Страница 23: ...3 OPERATING PRINCIPLES 3 6 DTP B Digital Transformer Protection GEK 106243E ...
Страница 53: ...10 INSTALLATION AND MAINTENANCE 10 2 DTP B Digital Transformer Protection GEK 106243E ...
Страница 66: ...12 FIGURES GEK 106243E DTP Digital Transformer Protection 12 1 12 FIGURES Figure 1 External Connections ...
Страница 67: ...12 FIGURES 12 2 DTP B Digital Transformer Protection GEK 106243E Figure 2 Panel Drilling Dimensions ...
Страница 68: ...12 FIGURES GEK 106243E DTP Digital Transformer Protection 12 3 Figure 3 RS 232 Connection ...
Страница 69: ...12 FIGURES 12 4 DTP B Digital Transformer Protection GEK 106243E Figure 4 Dimensions Diagram ...
Страница 70: ...12 FIGURES GEK 106243E DTP Digital Transformer Protection 12 5 Figure 5 Front View ...
Страница 73: ...12 FIGURES 89 DTP B Digital Transformer Protection GEK 106243E Figure 8 Block Diagram of the Protection ...