9. ACCEPTANCE TESTS
GEK-106243E
DTP Digital Transformer Protection
9-3
9.6 DIGITAL INPUTS CHECKING
For this test, the minimum and maximum admissible voltages will be applied to the inputs with a 20% rated
voltage tolerance.
Apply voltage to an input and check that the unit recognizes its activation by means of GE-LOCAL software.
Repeat the test for the rest of inputs.
9.7 OUTPUTS CHECKING
9.7.1 TRIP OUTPUTS CHECKING.
1.
Activate EP3 inputs, terminals J2-K2.
2. Verify that the tripping contacts (TRIP1, TRIP2, TRIP3, TRIP4) close when the input is applied, and open
when this condition disappears.
9.7.2 ALARM OUTPUTS CHECKING.
1.
Without powering the unit, check that the alarm output is closed.
2.
Apply power supply to the unit, and check that there is no alarm condition such as, protection out of service,
or disabled trips. In this case, check that the alarm contact is open.
9.7.3 CONFIGURABLE OUTPUTS CHECKING.
Make one of the configurable contacts close in one of the following ways:
1.
Activate an 87 trip in phase A and check that J5-K5 closes.
2.
Activate an 87 trip in phase B and check that J6-K6 closes.
3.
Activate an 87 trip in phase C and check that J7-K7 closes.
4.
Activate an 87B trip in phase A and check that J8-K8 closes.
5.
Activate an 87B trip in phase B and check that J9-K9 closes.
6.
Activate an 87B trip in phase C and check that J10-K10 closes.
7.
Activate PI2 input, terminals K1-K4 and check that J11-K11 closes.
8.
Activate PI4 input, terminals K2-K4 and check that J12-K12 closes.
9.
Check that all the configurable relays close with the closing condition, and open when it disappears.
Содержание DTP-B
Страница 23: ...3 OPERATING PRINCIPLES 3 6 DTP B Digital Transformer Protection GEK 106243E ...
Страница 53: ...10 INSTALLATION AND MAINTENANCE 10 2 DTP B Digital Transformer Protection GEK 106243E ...
Страница 66: ...12 FIGURES GEK 106243E DTP Digital Transformer Protection 12 1 12 FIGURES Figure 1 External Connections ...
Страница 67: ...12 FIGURES 12 2 DTP B Digital Transformer Protection GEK 106243E Figure 2 Panel Drilling Dimensions ...
Страница 68: ...12 FIGURES GEK 106243E DTP Digital Transformer Protection 12 3 Figure 3 RS 232 Connection ...
Страница 69: ...12 FIGURES 12 4 DTP B Digital Transformer Protection GEK 106243E Figure 4 Dimensions Diagram ...
Страница 70: ...12 FIGURES GEK 106243E DTP Digital Transformer Protection 12 5 Figure 5 Front View ...
Страница 73: ...12 FIGURES 89 DTP B Digital Transformer Protection GEK 106243E Figure 8 Block Diagram of the Protection ...