3.
Specification
I T E M S
S P E C I F I C A T I O N
Measuring Type
Diffusion
Measuring Value Display
Local Digital LCD or OLED Display
Means Value Display
Back light, 2-line/8-Characters LCD or OLED
Approval
Ex d IIC T6
Detectible Gas
Toxic Gas
Measuring Method
Electro-Chemical Cell
Heated-semiconductor Cell
Measuring Range
Refer to appendix.
Response Time
90% of full Scale in less than 45 sec
Accuracy
± 3% / Full Scale
Zero Drift
Less than 2% full Scale
Operating Temp.
-20 to 60℃
Operating Humidity
5 to 99% RH (Non-condensing)
Signal Output
Measuring Output: 4 – 20mA.DC / Full Scale
Test Output: 3mA
Calibration Output: 3mA
Fault Output: 2mA
HART
®
Interface
HART REV7 / Optional Board
(Note 1)
Calibration Work
Magnetic interface to configure Alarm
Cable Connection Length
Max. 2,500m : 4-20mA Signal
Power Supply
18 - 31V DC (24V DC / 60mA)
With alarm device (24V DC / 110mA)
Conduit Connection
1/2” or 3/4”PF, NPT(Standard : 3/4” PF)
Signal Cable Connection
(CVVS or CVVSB 1.5sq↑×3 wires) + Shield
Option
HART
®
Interface Board
GTL-100( Explosion-proof Warning Light )
Rain Cover
Dimensions
136(W) × 166(H) × 110 (D) mm
Weight
App. 1.5kg
[Table 1. GTD2000-Tx Specification]
Note 1) For HART, refer to GTD2000 HART® Field Device Specification