Menu Configuration Table
Level1
Level2
DEFAULT
NAME
PARAMETER
PROGRAM
MODE
GAS TYPE
(Gas Type)
[DEFIN./USER]
DEFIN.
GAS SEL
(Gas Select)
See Table 8
COMB.
UNIT SEL
(Unit Select)
%/%LEL/PPM/PPB
%LEL
D-POINT
(Decimal Point)
0.100/1.00/10.0/100
100
HIGH SCL
(High Scale)
1~10000
100
PASSWORD
00~99
00
CALIBRA.
MODE
(Calibration Mode)
CALIBRA.
[ZERO]
(Calibration Zero)
ZERO CAL
[NO,YES]
[NO]
ZERO GAS
[ 0]
ZERO >>>>
[SUCCESS / FAIL]
CAL. DATA
[ 0/ FAIL]
CALIBRA.
[SPAN]
(Calibration Span)
SPAN CAL
[NO , YES]
[NO]
SPAN GAS
[ 0]
SPAN SET
[ 50/ FAIL]
50
SPAN >>>>
[SUCCESS / FAIL ]
CAL. DATA
[ 0]
ALARM MODE
ALM USED
(Alarm Used)
[OFF / ON]
OFF
AL LATCH
(Alarm Latch)
[OFF / ON]
OFF
A1 LEVEL
(Alarm-1 Level)
[1 ~ 9999]
20
A1 TYPE
(Alarm-1 Type)
[INC / DEC]
INC
A1 DBAND
(Alarm-1 Dead Band)
[0.0 ~ 10.0%F]
1.0
A1 TIME
(Alarm-1 Time)
[0~ 60]SEC
1
A2 LEVEL
(Alarm-2 Level)
[1 ~ 9999]
40
A2 TYPE
(Alarm-2 Type)
[INC / DEC]
INC
A2 DBAND
(Alarm-2 Dead Band)
[0.0 ~ 10.0%F]
1.0
A2 TIME
(Alarm-2 Time)
[0~ 60]SEC
1
SENSOR MODE
SEN. OUT
(Sensor Output)
[ X.X mV ]
-
SEN. S/T
(Sensor sensitivity)
[ X.X ]
-
MZ / MS
(Manual Zero/Span)
X.X / XX.X
1.0 / -100.0
AZ / AS
(Auto Zero / Auto Span)
X.X / XX.X
1.0 / -100.0