1. Operator controls / arrangement
6
1.3 Menu structure (values are examples)
+
INPUT 1:
FREE
:
OUTPUT 4
OFF
DESIGN PRESS
13.0bar
START PROTECT
0.8bar
EXT. LIMIT
3650RPM
FINAL TEMP WARN
110ºC
FINAL TEMP MAX
120ºC
MIN START TEMP
1ºC
RUN-ON TIME
90s
SOFT STOP
30s
VOL.MAX.
2.8m3/min
VOL.MIN.
1.0m3/min
SOFTWARE:
DPro-LRS-1.00
TH 08.02.07
13:55:41
1 _____________00:00 00:00
:
7 _____________00:00 00:00
:
p
2
1 ___________00:00 00:00
:
p
2
7 ___________00:00 00:00
02!EM-STOP
12345h
01!EM-STOP
12300h
:
:
CUT-OUT POINT
13.0bar
TARGET PRESSURE
12.5bar
p
2
CUT-OUT POINT
10.5bar
p
2
TARGET PRESSURE 10.0bar
AUTOMATIC OPERATION
DISPLAY UNITS
m3/min
ENABLE REMOTE-START
OFF
TIMER CONTROL
OFF
p
2
TIMER CONTROL
OFF
AUTO RESTART
OFF
POWER LOSS TIME
2s
START-UP DELAY
5s
DRYER PRE-RUN
0min
RS485-PROTOCOL
ModBus
RS485-BAUDRATE
19200
RS485-ADDRESS
1
[MAINTENANCE SCHED.]
[ TIMER CONTROL ]
[ FAULT MEMORY ]
[ CONTROL MENU ]
[OPTIONAL IN-/OUTPUTS]
[ LIMIT VALUES ]
TOTAL RUNNING
12345h
LOADED HOURS
10987h
AIR FILTER IN
2000h
OIL FILTER IN
2000h
SEPARATOR IN
4000h
OIL CHANGE IN
4000h
SHUTDOWN
OFF
+
+
+
+
+
+