5. Extended functions 

20 

To do this, go to the 

[OPTIONAL

 

IN-/OUTPUTS] 

menu where you must program one input with the 

OPERATE_B1

 function. The unit can now be switched to 

off-load using the input.  

You will find a circuit diagram in Fig. 6.  

5.8.3  Remote start / stop 

 

Danger  

In this operating mode, the compressor may start 
automatically at any time. 

 

Attention  

Only potential-free contacts may be connected to 
the terminal strip. External voltages will destroy the 
GD Pilot.  

The potential-free contacts must not be more than 
20 metres away from the terminal strip. If necessary 

 

coupling relays must be fitted in the control 
cabinet.  

This function allows the operator to externally switch 
the compressor on and off. You have two ways of 
implementing this function. The remote start / stop 
function is permanently programmed (terminals see 
circuit diagram). 

The unit continues to run while the potential-free 
contact is closed. If the contact is opened, the soft-stop 
is undertaken and the unit stops. 

 

Note   

The unit is controlled using the remote start / stop 
function. If the unit is shut down during operations, e.g. 
due to power loss, it does not automatically start up 
when the power is restored.  The potential-free contact 
must first be re-opened and then closed to restart the 
unit. 
 

1st option

 

The compressor is to be activated using a potential-free 
contact. 

You activate this function in the 

[

 

CONTROL

 

MENU

 

]

 

sub-menu. Please go to the 

ENABLE

 

REMOTE-START

 

menu item. Once you have pressed the 

 

key, the 

OFF

 

value starts to flash. You can now use the 

  

key to 

change the value to 

ON

. The 

symbol appears in the 

first display row.  

Please connect the potential-free contact that you need 
for the remote start / stop function to the corresponding 
terminals (see circuit diagram). This input is 
permanently programmed for the remote start  / stop 
function. 

If the remote start / stop function is activated, you can 
no longer control the machine using the On  

I     

and 

  

 

keys on the GD Pilot. Only the emergency off button 
remains activated. The machine can now only be 
switched on and off using the potential-free contact. 

 

2nd option 

A control room is to decide whether the enable for the 
remote start / stop function is issued. The function for 
the enable is implemented using a digital input. If the 
enable is issued, the compressor can only be switched 
on and off using the external potential-free contact 
(terminals see circuit diagram). If the enable is not 
issued, the compressor can only be switched on and off 
on the GD Pilot.  

Please connect the potential-free contact that you need 
for the remote start / stop function to the corresponding 
terminals (see circuit diagram). This input is 
permanently programmed for the remote start  / stop 
function. 

In the 

[OPTIONAL

 

IN-/OUTPUTS] 

menu you now 

have to program one input with the 

ENAB.REM-START

 

function  (see section 5.5.1).  

The 

symbol appears in the first display row. In the 

[

 

CONTROL

 

MENU

 

]

 sub-menu behind the 

ENABLE

 

REMOTE-START

 menu item, 

EXT.

 appears. 

If the input is closed, the unit can only be switched on 
and off using the potential-free contact.  

If the input is opened, the unit can only be switched on 
and off using the GD Pilot. 

 

 

Содержание GD Pilot

Страница 1: ...GB Id no ZS1090606 01 June 2014 1 Original User Manual GD Pilot Electronics for speed controlled stationary rotary screw compressor VS 7 VS 22...

Страница 2: ......

Страница 3: ...l strip of the frequency converter by measuring this between the DC and DC terminals the exact position can be found in the supplied operating manual of the frequency converter between the DC terminal...

Страница 4: ...10 4 2 Programming maintenance intervals 10 4 3 Total load hours counter 10 5 Extended functions 11 5 1 CONTROL MENU sub menu 11 5 1 1 Operating modes 11 5 1 2 Second pressure range p2 11 5 1 3 Dryer...

Страница 5: ...sor stage Final compression pressure is the pressure measured downstream of the compressor stage Line pressure is the pressure within the system connected downstream of the compressor The following sy...

Страница 6: ...ically following the pressure requirement from your system WARNING START AFTER alternating with DE PRESSURISE The unit has been switched on and is ready However the internal unit pressure is above the...

Страница 7: ...see section 3 4 SOFT STOP TIME in xxs The system has been switched off The unit stops after the soft stop time of xx seconds FAULT fault text The unit has been shut down due to a fault You will find e...

Страница 8: ...___________00 00 00 00 02 EM STOP 12345h 01 EM STOP 12300h CUT OUT POINT 13 0bar TARGET PRESSURE 12 5bar p2 CUT OUT POINT 10 5bar p2 TARGET PRESSURE 10 0bar AUTOMATIC OPERATION DISPLAY UNITS m3 min EN...

Страница 9: ...CONTROL MENU FAULT MEMORY TIMER CONTROL LIMIT VALUES OPTIONAL IN OUTPUTS Enter a sub menu by pressing the key Again here you can use the or keys to go to a menu item To exit the sub menu you must pre...

Страница 10: ...correct increase or decrease this value using or Then confirm the value set by pressing the key Note The control system checks whether the value set can be used The maximum line pressure CUT OUT POINT...

Страница 11: ...requirement from the compressed air system and the unit is in CONTINUOUS OPERATION it switches to OFF LOAD This means that the motor and compressor stage run but no air is pumped into the compressed a...

Страница 12: ...t the maintenance interval should be reprogrammed The maintenance message can be acknowledged using the key 4 2 Programming maintenance intervals To program a maintenance interval please go to the MAI...

Страница 13: ...for the second pressure range function in the CONTROL MENU sub menu The relevant menu items there are p2CUT OUT POINT 10 5bar p2TARGET PRESSURE 10 0bar p2TIMER CONTROL OFF You can use p2CUT OUT POINT...

Страница 14: ...features several compressors This in turn ensures that the power supply is not loaded unnecessarily 5 1 6 Unlimited autom re start after power loss The control system can perform an automatic re star...

Страница 15: ...go to the warning message or fault that you are interested in in the fault memory The information set out above relating to the status of the compressor at the time of the fault can be called up in t...

Страница 16: ...is case 1 S______ 22 00 00 00 a 2 _MTWTFS 00 00 12 00 b 3 _MTWTF_ 12 30 00 00 c 4 ______S 12 30 14 00 d 5 _______ 00 00 00 00 6 _______ 00 00 00 00 7 _______ 00 00 00 00 a Start of operating period b...

Страница 17: ...values in your unit may be different a This is your unit s operating pressure This is also stamped on the compressor s name plate b To protect the compressor stage the compressor only starts up when t...

Страница 18: ...ontact is opened the DRYER WARNING warning message appears on the display the indication is delayed by 1 sec This function does not result in the unit shutting down BEKOMAT FAULT If the line pressure...

Страница 19: ...for the remote start RUNNING The output relay is activated when the compressor s motor is running is switched on 2nd PR RANGE The output relay is activated when the 2nd pressure range is applicable T...

Страница 20: ...all three codes If you have correctly entered the codes the machine will have automatically been switched to its delivery status The language has now been reset to English If you need a different lan...

Страница 21: ...ection 5 5 1 and circuit diagram In the OPTIONAL IN OUTPUTS menu you have to program the inputs using the 2nd PR RANGE function A potential free contact can now be connected to the terminal strip of t...

Страница 22: ...essed the key the OFF value starts to flash You can now use the key to change the value to ON The symbol appears in the first display row Please connect the potential free contact that you need for th...

Страница 23: ...trol transformer must be set to any local deviating mains voltages see circuit diagram 3 The switch panel temperature must not exceed 55 C 4 All remote controls fitted at a later date remote On Off mu...

Страница 24: ...ng operated with enclosure open Close enclosure Oil injection volume temperature too low high Check find cause Incorrect oil grade viscosity Check replace oil if necessary R2 temperature sensor defect...

Страница 25: ...rnal fault monitored by INPUT EXT FAULT 3 Check find cause WARNING EXT WARNING Warning from external device monitored by INPUT EXT WARNING 3 Check find cause FAULT BEKOMAT FAULT Connected condensate d...

Страница 26: ...he red Stop button on the frequency converter VSD was pressed while the compressor was running Always switch the compressor off via the GD Pilot FAULT VSD FAULT xx The frequency converter VSD detected...

Страница 27: ...received no commands from the GD Pilot Check wiring of the Modbus interface FAULT E500 FAULT E501 The frequency converter was faulty or not programmed replacement device so it had to be reprogrammed f...