5. Extended functions 

11 

Exten de d f un cti on s 

5.1   [ CONTROL MENU ]  sub-menu 

The most important parameters of the 

[

 

CONTROL

 

MENU

 

]

 

menu have already been explained in section 2 Default 
settings. This section simply contains an overview and 
explanation of additional (extended) functions.  

 

5.1.1  Operating modes 

Go to the  

[

 

CONTROL

 

MENU

 

]

 sub-menu and use the

 

 

key to go to the  

AUTOMATIC

 

OPERATION

 menu item. If 

you press the 

 

key, the 

AUTOMATIC

 

OPERATION

 

value starts to flash. You can use the 

  

key to now 

switch to  

CONTINUOUS

 

OPERATION

. Confirm a set 

value by pressing the 

 

key. 

You can choose from two operating modes: 

AUTOMATIC OPERATION 

AUTOMATIC

 

OPERATION 

is the most economical of 

your compressor's operating modes. If there is no need 
for compressed air in your system, the compressor is 
shut down after the 

RUN-ON

 

TIME

. The control system 

automatically recognises when compressed air is 
needed again. The unit then starts up straight away. 

CONTINUOUS OPERATION 

CONTINUOUS

 

OPERATION

 is only needed for some 

special applications. When in this operating mode, the 
motor is not shut down if there is no longer any need for 
pressure. The compressor stage now runs continually 
in off-mode when there is no need for pressure.  

 

5.1.2  Second pressure range (

p

2

The range between the maximum pressure and the 
target pressure is called the pressure range. The 
second pressure range function allows you to use 
another pressure range in addition to the pressure 
range already set (see section 2.2). This could be used 
to for example implement night-time lowering.  

You will find the settings for the second pressure range 
function in the  

[

 

CONTROL

 

MENU

 

]

 sub-menu. The 

relevant menu items there are: 

p

2

CUT-OUT

 

POINT 

10.5bar

 

p

2

TARGET PRESSURE 

10.0bar

 

p

2

TIMER

 

CONTROL 

OFF

 

 

You can use 

p

2

CUT-OUT

 

POINT 

and 

p

2

TARGET 

PRESSURE

 to set the line pressure switching points. 

Use the 

p

2

TIMER

 

CONTROL On

 menu item to activate 

the timer for the second pressure range. 

You also can activate / deactivate the second pressure 
range using an external potential-free contact (see 
section 5.5). 

Section 5.3.2 contains a description of how to set the 
timer for the second pressure range. 

 

Note  

The values shown are examples only. The values used 
in your unit may be different. 

 

5.1.3  Dryer pre-run 

If you are using an external dryer, you can provide the 
dryer with a specified pre-run time. The compressor is 
then only started after this pre-run time. 

To set the pre-run time, please go to the 

[

 

CONTROL

 

MENU

 

]

 sub-menu. From there use the 

    

key to go to the 

DRYER

 

PRE-RUN 0min

 menu item. 

Once you have pressed the 

 

key, the 

0min

 value 

starts to flash. You can now use the  

  

or

 

 

 keys to 

set the pre-run time you want. Then confirm your entry 
using the 

 

key. 

 

5.1.4  RS 485 communication 

You can perform the settings for RS 485 
communication in the  

[

 

CONTROL

 

MENU

 

]

 sub-menu. 

The  

RS485-PROTOCOL 

ModBus 

RS485-BAUDRATE 

19200 

RS485-ADDRESS 

menu items are of relevance. 

The GD Pilot has a serial RS485 interface. This 
interface uses the ModBus RTU protocol.  

ModBus interfaces and drivers are available from many 
of the well-known manufacturers of programmable logic 
controllers (PLC). 

You can set the baud rate you want in the

 RS485-

BAUDRATE

 menu item. 

You can set the participant number you want in the 

 

RS485-ADDRESS

 menu item. 

 

Note  

The values shown are examples only. The values used 
in your unit may be different. 

 

Содержание GD Pilot

Страница 1: ...GB Id no ZS1090606 01 June 2014 1 Original User Manual GD Pilot Electronics for speed controlled stationary rotary screw compressor VS 7 VS 22...

Страница 2: ......

Страница 3: ...l strip of the frequency converter by measuring this between the DC and DC terminals the exact position can be found in the supplied operating manual of the frequency converter between the DC terminal...

Страница 4: ...10 4 2 Programming maintenance intervals 10 4 3 Total load hours counter 10 5 Extended functions 11 5 1 CONTROL MENU sub menu 11 5 1 1 Operating modes 11 5 1 2 Second pressure range p2 11 5 1 3 Dryer...

Страница 5: ...sor stage Final compression pressure is the pressure measured downstream of the compressor stage Line pressure is the pressure within the system connected downstream of the compressor The following sy...

Страница 6: ...ically following the pressure requirement from your system WARNING START AFTER alternating with DE PRESSURISE The unit has been switched on and is ready However the internal unit pressure is above the...

Страница 7: ...see section 3 4 SOFT STOP TIME in xxs The system has been switched off The unit stops after the soft stop time of xx seconds FAULT fault text The unit has been shut down due to a fault You will find e...

Страница 8: ...___________00 00 00 00 02 EM STOP 12345h 01 EM STOP 12300h CUT OUT POINT 13 0bar TARGET PRESSURE 12 5bar p2 CUT OUT POINT 10 5bar p2 TARGET PRESSURE 10 0bar AUTOMATIC OPERATION DISPLAY UNITS m3 min EN...

Страница 9: ...CONTROL MENU FAULT MEMORY TIMER CONTROL LIMIT VALUES OPTIONAL IN OUTPUTS Enter a sub menu by pressing the key Again here you can use the or keys to go to a menu item To exit the sub menu you must pre...

Страница 10: ...correct increase or decrease this value using or Then confirm the value set by pressing the key Note The control system checks whether the value set can be used The maximum line pressure CUT OUT POINT...

Страница 11: ...requirement from the compressed air system and the unit is in CONTINUOUS OPERATION it switches to OFF LOAD This means that the motor and compressor stage run but no air is pumped into the compressed a...

Страница 12: ...t the maintenance interval should be reprogrammed The maintenance message can be acknowledged using the key 4 2 Programming maintenance intervals To program a maintenance interval please go to the MAI...

Страница 13: ...for the second pressure range function in the CONTROL MENU sub menu The relevant menu items there are p2CUT OUT POINT 10 5bar p2TARGET PRESSURE 10 0bar p2TIMER CONTROL OFF You can use p2CUT OUT POINT...

Страница 14: ...features several compressors This in turn ensures that the power supply is not loaded unnecessarily 5 1 6 Unlimited autom re start after power loss The control system can perform an automatic re star...

Страница 15: ...go to the warning message or fault that you are interested in in the fault memory The information set out above relating to the status of the compressor at the time of the fault can be called up in t...

Страница 16: ...is case 1 S______ 22 00 00 00 a 2 _MTWTFS 00 00 12 00 b 3 _MTWTF_ 12 30 00 00 c 4 ______S 12 30 14 00 d 5 _______ 00 00 00 00 6 _______ 00 00 00 00 7 _______ 00 00 00 00 a Start of operating period b...

Страница 17: ...values in your unit may be different a This is your unit s operating pressure This is also stamped on the compressor s name plate b To protect the compressor stage the compressor only starts up when t...

Страница 18: ...ontact is opened the DRYER WARNING warning message appears on the display the indication is delayed by 1 sec This function does not result in the unit shutting down BEKOMAT FAULT If the line pressure...

Страница 19: ...for the remote start RUNNING The output relay is activated when the compressor s motor is running is switched on 2nd PR RANGE The output relay is activated when the 2nd pressure range is applicable T...

Страница 20: ...all three codes If you have correctly entered the codes the machine will have automatically been switched to its delivery status The language has now been reset to English If you need a different lan...

Страница 21: ...ection 5 5 1 and circuit diagram In the OPTIONAL IN OUTPUTS menu you have to program the inputs using the 2nd PR RANGE function A potential free contact can now be connected to the terminal strip of t...

Страница 22: ...essed the key the OFF value starts to flash You can now use the key to change the value to ON The symbol appears in the first display row Please connect the potential free contact that you need for th...

Страница 23: ...trol transformer must be set to any local deviating mains voltages see circuit diagram 3 The switch panel temperature must not exceed 55 C 4 All remote controls fitted at a later date remote On Off mu...

Страница 24: ...ng operated with enclosure open Close enclosure Oil injection volume temperature too low high Check find cause Incorrect oil grade viscosity Check replace oil if necessary R2 temperature sensor defect...

Страница 25: ...rnal fault monitored by INPUT EXT FAULT 3 Check find cause WARNING EXT WARNING Warning from external device monitored by INPUT EXT WARNING 3 Check find cause FAULT BEKOMAT FAULT Connected condensate d...

Страница 26: ...he red Stop button on the frequency converter VSD was pressed while the compressor was running Always switch the compressor off via the GD Pilot FAULT VSD FAULT xx The frequency converter VSD detected...

Страница 27: ...received no commands from the GD Pilot Check wiring of the Modbus interface FAULT E500 FAULT E501 The frequency converter was faulty or not programmed replacement device so it had to be reprogrammed f...

Страница 28: ......

Страница 29: ......

Страница 30: ......

Страница 31: ......

Страница 32: ...essor Division 1800 Gardner Expressway Quincy Illinois 62305 Telephone 800 682 9868 Fax 217 224 7814 Gardner Denver Deutschland GmbH Argenthaler Str 11 55469 Simmern Deutschland Tel 49 0 6761 832 0 Fa...

Отзывы: