13-21-611 Page 31
3-10
Setting the Load Pressure
1. Press the back button to return to the previous screen. The
Load/Unload Setpoints
menu will be
displayed.
2. From the
Load/Unload Setpoints,
use the navigational buttons and select
Load Pressure
.
3. Press the
Enter
button. The
Load Pressure
numeric keypad will appear as illustrated by Figure 3-
10
.
Figure 3- 10: Load Pressure Numeric Key Pad
4. Enter the
Load Pressure
to the first decimal by using the navigational buttons to choose the
appropriate numeric value as indicated by the white highlight (CLR in Figure 3-6). The
Select
button
is used to enter the number or function currently highlighted. When the load pressure has been
entered, navigate to and select ENTER when complete, or simply press the
Enter
button to apply
the value. If the value entered is within the valid range, the number will turn green in the entry pad
to show its acceptance. If the value is not accepted, the number will turn red momentarily and the
value displayed on the keypad will revert back to the current setting. If this occurs, check the value
entered against the
Min
and
Max
values above the keypad. The
Load Pressure
is the pressure
that the compressor will begin producing air again after unloading.
Содержание ELECTRA-SAVER G2
Страница 11: ...13 21 611 Page 10 1 3 Figure 1 4 COMPRESSOR MOTOR SIDE Figure 1 5 COOLER RESERVOIR SIDE 309EBD797 B Ref Drawing...
Страница 12: ...13 21 611 Page 11 1 4 Figure 1 6 AIR OIL FLOW DIAGRAM 307EBD797 B Ref Drawing...
Страница 41: ...4 10 THIS PAGE INTENTIONALLY LEFT BLANK 13 21 611 Page 40...
Страница 42: ...4 10 FIGURE 4 6 COMPRESSOR PACKAGE P ID 13 21 611 Page 41 300EBF797 02 Ref Drawing...
Страница 70: ...13 21 611 Page 69 5 4 Figure 5 3 FLOW DIAGRAM AIR OIL SYSTEM 300EBF797 02 Ref Drawing...
Страница 71: ...5 5 13 21 611 Page 70 Figure 5 4 OIL FLOW DIAGRAM REMOTE MOUNTED COOLER 318EBD797 00 Ref Drawing...
Страница 74: ...13 21 611 Page 73 5 8 THIS PAGE INTENTIONALLY LEFT BLANK...