13-21-611 Page 19
2-8
The heat exchanger system is designed to operate with water inlet temperatures from 60
F to 90
F (16
C to 32
C) and a water outlet temperature not to exceed 110
F (43
C). If water colder than 60
F is used,
high water outlet temperatures (over 110
F, 43
C) will be experienced along with shortened heat
exchanger life caused by tube fouling and corrosion. If water warmer than 90
F (32
C) is used, higher
compressor oil inlet temperatures and high water usage will result.
Most water systems will require control of impurities: filtration, softening or other treatment. See Section 5,
“Compressor Oil Cooler - Water-Cooled Heat Exchanger” for more information on the water system.
Figure 2-7
– SERIES PIPING
SERIES PIPING
(Figure 2-7) - Water flow must be through aftercooler first for effective cooling of discharge
air and is so piped on the standard water-cooled unit.
Figure 2-8
– PARALLEL PIPING
304EBD797-C
(Ref. Drawing)
304EBD797-C
(Ref. Drawing)
Содержание ELECTRA-SAVER G2
Страница 11: ...13 21 611 Page 10 1 3 Figure 1 4 COMPRESSOR MOTOR SIDE Figure 1 5 COOLER RESERVOIR SIDE 309EBD797 B Ref Drawing...
Страница 12: ...13 21 611 Page 11 1 4 Figure 1 6 AIR OIL FLOW DIAGRAM 307EBD797 B Ref Drawing...
Страница 41: ...4 10 THIS PAGE INTENTIONALLY LEFT BLANK 13 21 611 Page 40...
Страница 42: ...4 10 FIGURE 4 6 COMPRESSOR PACKAGE P ID 13 21 611 Page 41 300EBF797 02 Ref Drawing...
Страница 70: ...13 21 611 Page 69 5 4 Figure 5 3 FLOW DIAGRAM AIR OIL SYSTEM 300EBF797 02 Ref Drawing...
Страница 71: ...5 5 13 21 611 Page 70 Figure 5 4 OIL FLOW DIAGRAM REMOTE MOUNTED COOLER 318EBD797 00 Ref Drawing...
Страница 74: ...13 21 611 Page 73 5 8 THIS PAGE INTENTIONALLY LEFT BLANK...