GAT NET.Lock 7000 System
Electrical Connection
www.gantner.com
HB_GAT-NETLOCK7000--EN_30
29
4.4 Connections at the Master Controller GAT NET.Controller M 7000
4.4.1 Connection of the Slave Controllers GAT NET.Controller S 7000 to the Master Controller
The slave controllers are connected to the master controllers via the RS 485 interface using RJ 45 plugs. The con-
nection must be made at the "RS 485 SLAVES" socket.
Figure 4.11
- Connection of the GAT NET.Controller S 7000 at the GAT NET.Controller M 7000
Note:
The "RS 485 ADD-ON" connector is reserved for future requirements and must not be used to connect the
slave controllers.
Observe the following values for the number of connectable controllers per master controller (RS 485 line):
- A maximum of 8 slave controllers per master controller, i.e. per RS 485 line
- Maximum length of one RS 485 line = 200 m
4.4.2 Ethernet Connection
The connection of several GAT NET.Controller M 7000 as well as the connection of the master controller to a
PC/server is performed via Ethernet. The Ethernet line is connected at the RJ 45 plug on the back side of the GAT
NET.Controller M 7000.
Figure 4.12
- Connection of the GAT NET.Controller M 7000 to Ethernet