GAT NET.Lock 7000 System

 

Electrical Connection 

 

www.gantner.com

  

HB_GAT-NETLOCK7000--EN_30

 

25

 

4.3  Connections at the Slave Controller GAT NET.Controller S 7000 

 
 

4.3.1  GAT NET.Lock 7000 Connection 

 

 

The locks GAT NET.Lock 7000 are connected via the 4-pin MOLEX connectors on the sockets at the side panel of 
the GAT NET.Controller S 7000. 
 

Attention,

 always use the original cables of GANTNER Electronic GmbH. The connection cable of the lock 

must not be modified (shortened or extended). If the cable is too short, only one GANTNER extension cable 
GAT Net.Lock Cable 4m (partno.: 321826, length = 4 m) may be used. The maximum cable length between 
the GAT NET.Lock 7000 and the slave controller thus being 8 m. 

 
Up to 24 GAT NET.Lock 7000 can be connected to one slave controller. The locks are controlled and differentiated 
via the channel numbers indicated at the side panel of the slave controller. Therefore it is important where the locks 
are connected and how the locking system is configured. 
 
The slave controller should be located in such a manner, that the locks can be connected with the minimum length of 
cables (e.g. directly on the lockers). 
 

 

 

Figure 4.3 

- Connection to the GAT NET.Lock 7000 to a slave controller GAT NET.Controller S 7000 

 

Note: 

Do not attempt to connect the RFID locker locks GAT NET.Lock 7000 to a GAT Smart.Controller S 7000 as 
this smart controller only operates with GAT Smart.Locks 7001. For the GAT NET.Lock 7000, you have to use 
the GAT NET.Controller S 7000 slave controller.

 

 
 
 

4.3.2  Network Connection 

 
The slave controllers are interconnected with each other via the serial RS 485 interface. The same RS 485 interface 
is used to connect the slave controllers to a GAT NET.Controller M 7000 master controller. 
RJ 45 plugs are used for connecting the RS 485 cables at the GAT NET.Controller S 7000. For the network connection 
we recommend to use at least a CAT 5 (STP) cable. 
 

 

 

Figure 4.4 

- RS 485 connection on the GAT NET.Controller S 7000 

Содержание GAT NET.Lock 7000

Страница 1: ...www gantner com HB_GAT NETLOCK7000 EN_30 1 GAT NET Lock 7000 System Electronic RFID Locker Locks Installation Configuration Operation Document Version 3 0...

Страница 2: ...GAT NET Lock 7000 System 2 HB_GAT NETLOCK7000 EN_30 www gantner com...

Страница 3: ...s case contact your customer advisor He will make every effort to resolve the problem as quickly as possible 7 Installation commissioning and servicing of our appliances must only be carried out by su...

Страница 4: ...y we still look forward to hear from you We wish you a successful application of our appliances We will be pleased to welcome you as a customer again soon Contact address manufacturer GANTNER Electron...

Страница 5: ...00 at Metallic Doors 20 3 7 Points to be observed during Installation 21 3 8 Test Installation 21 3 9 Replacement after a Burglary Attempt 21 4 Electrical Connection 23 4 1 System Structure 23 4 2 Cab...

Страница 6: ...6 HB_GAT NETLOCK7000 EN_30 www gantner com 5 6 GAT Relaxx Operation Software for GAT NET Lock 7000 System 34 5 6 1 User Interface 34 6 Technical Data 37 6 1 GAT NET Lock 7000 37 6 2 GAT NET Controller...

Страница 7: ...mounting procedure of the locks and bolt sets with all important measures and information can be found Because there are many different types of lockers available the mounting procedure is written in...

Страница 8: ...t 7 GAT NET Power Plug 5 GAT NET Controller M 7000 Master Controller 1 GAT NET Lock 7000 2 GAT NET Lock BoltSet 7100 for non metallic doors 10 GAT NET Lock Cable 4m connection cable length 4 m 3 GAT N...

Страница 9: ...T Controller S 7000 8 GAT NET Lock Tool 7000 Center punch gauge for bolt mounting in the locker doors With these gauges the drillings for the mounting can be easily marked on the locker doors 9 GAT NE...

Страница 10: ...GAT NET Lock 7000 System General Information 10 HB_GAT NETLOCK7000 EN_30 www gantner com...

Страница 11: ...tware from GANTNER Electronic GmbH on a host computer server Using a locker The user closes the door of a free locker and while holding the door shut puts his data carrier onto the reading centre at t...

Страница 12: ...rs The bolt sets for the GAT NET Lock 7000 already include boosters 1 in the GAT NET Lock BoltSet 7100 for non metallic doors and 2 in the GAT NET Lock BoltSet 7200 for metallic doors GAT Relaxx PC so...

Страница 13: ...of the opening direction of lockers left right In the following pages the mounting for right hinged doors is desribed The installation process for left locker doors is in principle the same as for ri...

Страница 14: ...Mounting 3 3 1 Door Width The minimum door width allowed measured from the door shackle to the hinge is 230 mm If the door is narrower the door shackle would hit the locker when the door is being clo...

Страница 15: ...oors 1 GAT NET Lock 7000 2 GAT NET Lock BoltSet 7100 for non metallic doors 3 GAT NET Lock BoltSet 7200 for metallic doors 4 Door shackle 5 Door contact 6 Booster 7 Status LED 8 Label carrier 3 4 Door...

Страница 16: ...material 4 Door shackle 5 Door contact 6 Mounting screws for bolt set 7 LED hole in the locker door Figure 3 5 Mounting of the GAT NET Lock 7000 in a locker with non metallic door right door 3 5 1 Imp...

Страница 17: ...he 3 holes according to the information in 3 5 1 Important Measures when Mounting the GAT NET Lock 7000 and Bolt Set Non Metal Doors Plug in the connection cable at the GAT NET Lock 7000 see 4 Electri...

Страница 18: ...ide door sheet The two parts of the GAT NET Lock Bolt Set 7200 are then mounted into the locker door See the following figure and the steps afterwards for the mounting instructions 1 GAT NET Lock 7000...

Страница 19: ...m see Figure 3 7 When the door is pressed shut the gap between the bolt set and the front of the GAT NET Lock 7000 must not exceed 0 5 mm see measure in Figure 3 7 Ideally the bolt set should touch th...

Страница 20: ...8 mm for the GAT NET Lock Bolt Set 7200 On the inner wall of the locker door drill the 4 holes 6 for mounting the GAT NET Lock Bolt Set 7200 On the outer wall of the locker door make the cut out 68 2...

Страница 21: ...rings or similar elements The locker door must open automatically without resistance when the GAT NET Lock 7000 unlocks the door 3 8 Test Installation As the GAT NET Lock 7000 is suitable for a wide r...

Страница 22: ...GAT NET Lock 7000 System Mounting 22 HB_GAT NETLOCK7000 EN_30 www gantner com...

Страница 23: ...e connection must only be done in powerless state and only by trained and specialised personnel 4 1 System Structure The GAT NET Lock 7000 are always connected to the slave controllers GAT NET Control...

Страница 24: ...andard connection cable is too short it is possible to use two of those cables which are connected together with the GAT NET Lock Connector For connection of the GAT NET Lock 7000 only use an original...

Страница 25: ...controller Therefore it is important where the locks are connected and how the locking system is configured The slave controller should be located in such a manner that the locks can be connected wit...

Страница 26: ...RS 485 line length It is important to differentiate between the RS 485 IN and OUT plugs Connect the incoming cable from the master Controller or the previous slave controller to the RS 485 IN plug an...

Страница 27: ...ower supply connections 1 The power supply can be connected to each slave controller individually 2 The power supply is connected to a single or a few slave controllers which in turn supply the remain...

Страница 28: ...T NET Controller S 7000 LEDs RS 485 IN yellow The connection with the master controller has been established RS 485 IN green RS 485 communication is active LED 1 blue Lock activated controlled LED 2 g...

Страница 29: ...ler M 7000 Note The RS 485 ADD ON connector is reserved for future requirements and must not be used to connect the slave controllers Observe the following values for the number of connectable control...

Страница 30: ...LED Signals and Buttons For the display of the operating state and to start certain functions various LED indicators and buttons are provided on the GAT NET Controller M 7000 Figure 4 14 LEDs and butt...

Страница 31: ...Locker In order to use an unused locker i e locking a locker the door must be pressed shut so that the door shackle moves into the GAT NET Lock 7000 While the door is kept shut the user must hold his...

Страница 32: ...out 5 seconds The configuration parameters will remain un changed 5 4 Delete Configuration Parameters of a Controller Reset to Default Settings After deleting the configuration parameters of a control...

Страница 33: ...r software green Normal operation connection to master controller and server software is OK alternately red green blinking Bootloader mode a firmware update is currently being loaded or there is no fi...

Страница 34: ...the CD together with GAT Relaxx Furthermore the NET framework with version 4 0 or higher is required This is also included on the GAT Relaxx installation CD Installation and First Startup The GAT Rel...

Страница 35: ...ew Here the hardware of the entire system is defined Communication channels and connected controllers can be added and the lockers used can be defined per con troller 6 Locker overview Here the locker...

Страница 36: ...re based locker assignment to respective controllers 6 Locker overview Here the lockers of the selected area are displayed graphically The respecitve locker state is displayed by corresponding colours...

Страница 37: ...indoor areas 6 2 GAT NET Controller S 7000 Nominal voltage UDC 24 V Power supply unit External power supply units use only power supply units approved by GANT NER Electronic GmbH for the GAT NET Cont...

Страница 38: ...r memory expansion log files firmware update or person lists Digital inputs 4 x optocoupler Digital outputs 4 x relay Interface between slave and master RS 485 Interface between master and server Ethe...

Страница 39: ......

Страница 40: ...T 43 5556 73784 0 T 49 234 58896 0 T 61 2 9011 8114 F 43 5556 73784 8000 F 49 234 58896 11 F 61 2 8209 1708 info gantner com info de gantner com info aus gantner com GANTNER Electronics Ltd UK GANTNE...

Отзывы: