Scope of Work/Materials 

 
13850 (28 31 00) - 8 
 
Bid No.041818-Installation of New Fire Alarm System at Adams Elementary School 

3. 

Integral battery charger with capacity to charge up to 55 amp-hour batteries while under 
full load. 

 

D. 

Batteries: 
1. 

Sufficient capacity to provide power for entire system upon loss of normal AC power for a 
period of 24 hours with 15 minutes of alarm signaling at end of this 24-hour period, as 
required by NFPA 72, Local Systems. 

2. 

Sufficient capacity to provide power for entire system upon loss of normal AC power for a 
period of 60 hours with 15 minutes of alarm signaling at end of this 60-hour period, as 
required by NFPA 72, Auxiliary Systems. 

 

E. 

LCD Display Module (LCD-E3): 
1. 

LCD Display:  80-character RS-485 based textual annunciator with capability of being 
mounted locally or remotely.  Provides audible and visual annunciation of all alarms and 
trouble signals.  Provide dedicated LEDs for: 
a. 

AC Power On:  Green. 

b. 

Alarm:  Red. 

c. 

Supervisory:  Yellow. 

d. 

System Trouble:  Yellow. 

e. 

Power Fault:  Yellow. 

f. 

Ground Fault:  Yellow. 

g. 

System Silenced:  Yellow. 

2. 

80-Character Alphanumeric Display:  Provide status of all analog/addressable sensors, 
monitor and control modules.  Display shall be liquid crystal type (LCD), clearly visible in 
dark and under all light conditions. 

3. 

Panel shall contain 4 functional keys: 
a. 

Alarm Acknowledge. 

b. 

Trouble Acknowledge. 

c. 

Signal Silence. 

d. 

System Reset/Lamp Test. 

4. 

Panel shall contain 3 configuration buttons: 
a. 

Menu/Back. 

b. 

Back Space/Edit. 

c. 

OK/Enter. 

5. 

Panel shall have 12-key telephone-style keypad to permit selection of functions. 

 

F. 

Intelligent Loop Interface (ILI-MB-E3):  System shall be of multiprocessor design to allow 

maximum flexibility of capabilities and operation.  Intelligent Loop Interface shall be capable of 
mounting in stand-alone enclosure as specified. 

1. 

Field Programmable:  System shall be capable of being programmed by Field 
Configuration Program (FCP), allowing programming to be downloaded via portable 
computer from any node on network. 

2. 

RS-232C Serial Output:  Supervised RS-232C serial port shall be provided to operate 
remote printers and/or video terminals, accept downloaded program from portable 
computer, or provide 80-column readout of all alarms, troubles, location descriptions, time, 
and date.  Communication shall be standard ASCII code operating from 1,200 to 115,200 
baud rate. 

3. 

RS-485 Serial Output:  Each ILI-MB-E3 shall incorporate RS-485 bus via ribbon harness 
for connection of modules inside same cabinet, and via 4-wire quick connector for 

Содержание E3 Series

Страница 1: ...Data Interchange 2 RS 485 standard defining the electrical characteristics of drivers and receivers for use in balanced digital multipoint systems B National Fire Protection Association NFPA 1 NFPA 12...

Страница 2: ...ary power failure until alarm signal is processed and recorded 7 Network Node Communications a Communicated between panels on single pair of copper wires or fiber optic cables b To enhance system surv...

Страница 3: ...ean control by event programming including as a minimum AND OR NOT and Timer functions 6 Control Panels Capability to accept firmware upgrades via connection with laptop computer without requirement o...

Страница 4: ...uding elevator recall elevator power shutdown door lock release door holder release HVAC unit shutdown smoke evacuation system activation and stair pressurization fan activation 5 Bill of Material OWN...

Страница 5: ...bmittals and shop drawings letter of certification from Gamewell FCI indicating proposed engineered system distributor is an authorized representative in good standing of the equipment supplied Includ...

Страница 6: ...of devices circuits zones and changes to system operation and custom label changes for devices or zones 4 System structure and software shall place no limit on type or extent of software modification...

Страница 7: ...ly Module PM 9 with batteries 3 80 Character LCD Display LCD E3 4 Intelligent Loop Main Board Interface ILI MB E3 or ILI95 MB E3 5 Optional Intelligent Loop Supplemental Interface ILI S E3 or ILI95 S...

Страница 8: ...or and control modules Display shall be liquid crystal type LCD clearly visible in dark and under all light conditions 3 Panel shall contain 4 functional keys a Alarm Acknowledge b Trouble Acknowledge...

Страница 9: ...cuits on SLC or NAC circuits disarrangement in system wiring failure of microprocessor or any identification module or system ground faults shall activate this trouble circuit Trouble signal shall be...

Страница 10: ...ull 4100 event history log supporting local and network functions If a main processor or network node is lost the entire log shall be accessible at any other Loop Interface board This shall be demonst...

Страница 11: ...e alarm systems in accordance with NFPA 72 as it is impossible to test all functions and verify items such as annunciation with only 1 person 24 Signaling Line Circuits Each ILI MB E3 module shall pro...

Страница 12: ...from 64 nodes to 122 nodes ANX SR Addressable Node Expander Single Ring will function in single 64 node systems 3 ANX shall provide a Ethernet Port for use in Systems Integration and for use with Eme...

Страница 13: ...e Detectors Provide 2 status LEDs Both LEDs shall flash under normal conditions indicating detector is operational and in regular communication with control panel and both LEDs shall be placed into st...

Страница 14: ...trol panel send data to panel representing analog level of products of combustion F Intelligent Multi Criteria Acclimating Detectors MCS ACCLIMATE2F 1 Addressable device designed to monitor a minimum...

Страница 15: ...1 The detector shall be comprised of four sensing elements including a photoelectric light scattering particulate sensor an electrochemical CO sensor a daylight filtered infrared IR sensor and solid...

Страница 16: ...hange over air handling systems to help prevent rapid distribution of toxic smoke and fire gases throughout areas served by duct system 3 Duct Smoke Detectors Mounted Above Ceiling or Otherwise Obstru...

Страница 17: ...D to blink latch on or latch off Flash under normal conditions indicating monitor module is operational and in regular communication with control panel P Addressable Dry Contact Monitor Modules MMI 10...

Страница 18: ...module NAC Wire for Style Z or Style Y Class A B with up to 1 amp of inductive signal or 2 amps of resistive signal operation Relay coil shall be magnetically latched to reduce wiring connection requi...

Страница 19: ...nel D NGA Network Graphic Annunciator 1 Main Menu a Configure allows Auto configuration of ILI MB S and NGA or ANX b Walk Drill enables Walk Test and Fire Drill function c I O Allows enable disable in...

Страница 20: ...arm system devices control panels and remote annunciators in finished areas Flush mount or surface mount fire detection and alarm system devices control panels and remote annunciators in unfinished ar...

Страница 21: ...anufacturer representative of Owner and fire department shall operate every installed device to verify proper operation and correct annunciation at control panel 3 Open signaling line circuits and not...

Отзывы: