Scope of Work/Materials 

 
13850 (28 31 00) - 14 
 
Bid No.041818-Installation of New Fire Alarm System at Adams Elementary School 

B. 

Addressable Manual Stations (MS-7AF): 
1. 

Manual Fire Alarm Stations:  Non-code, non-break glass type, equipped with key lock so 
they may be tested without operating handle. 

2. 

Operated Station:  Visually apparent, as operated, at a minimum distance of 100 feet (30.5 
m) from front or side. 

3. 

Stations shall be designed so after actual activation, they cannot be restored to normal 
except by key reset. 

4. 

Manual stations shall be constructed of Lexan with clearly visible operating instructions 
provided on cover.  The word FIRE shall appear on front of stations in raised letters, 1.75 
inches (44 mm) or larger.    

5. 

Addressable manual stations shall, on command from control panel, send data to panel 
representing state of manual switch and addressable communication module status. 

 

C. 

Intelligent Thermal Detectors (ATD-RL2F): Intelligent addressable devices rated at 135 degrees 

F (58 degrees C) and have rate-of-rise element rated at 15 degrees F (9.4 degrees C) per 
minute.  Connect via 2 wires to fire alarm control panel signaling line circuit. 

 

D. 

Intelligent Photoelectric Smoke Detectors (ASD-PL2F):  Use photoelectric (light-scattering) 

principal to measure smoke density and shall, on command from control panel, send data to 
panel representing analog level of smoke density. 

 

E. 

Intelligent Ionization Smoke Detectors (ASD-IL2F):  Use dual-chamber ionization principal to 

measure products of combustion and shall, on command from control panel, send data to panel 
representing analog level of products of combustion. 

 

F. 

Intelligent Multi-Criteria Acclimating Detectors (MCS-ACCLIMATE2F): 
1. 

Addressable device designed to monitor a minimum of photoelectric and thermal 
technologies in single-sensing device.  Include ability to adapt to its environment by 
utilizing built-in microprocessor to determine its environment and choose appropriate 
sensing settings.  Allow wide sensitivity window, with no less than 1 to 4 percent per foot 
obscuration.  Utilize advanced electronics that react to slow smoldering fires and thermal 
properties within single sensing device. 

2. 

Microprocessor:  Capable of selecting appropriate sensitivity levels based on environment 
type it is in, such as office, manufacturing, or kitchen, and then have ability to 
automatically change setting as environment changes, as when walls are moved or as 
occupancy changes. 

3. 

Intelligent multi-criteria detection device shall include ability to combine signal of thermal 
sensor with signal of photoelectric signal to react hastily in event of fire situation.  Include 
inherent ability to distinguish between fire condition and false alarm condition by 
examining characteristics of thermal and smoke sensing chambers and comparing them to 
database of actual fire and deceptive phenomena. 

 

G. 

Intelligent Laser Detectors (ASD-LS):  Sensor device designed to use laser diode similar to way 

photoelectric sensor uses LEDs inside of sensing chamber.  Detector design shall allow wide 
sensitivity window, with no less than 0.2 to 4 percent per foot obscuration.  Detector shall be 
used as indicated in special application clean-room-type environments only. 

 

H. 

Intelligent 4 Element Multi-Criteria Detectors (MCS-4-WARN): 

Содержание E3 Series

Страница 1: ...Data Interchange 2 RS 485 standard defining the electrical characteristics of drivers and receivers for use in balanced digital multipoint systems B National Fire Protection Association NFPA 1 NFPA 12...

Страница 2: ...ary power failure until alarm signal is processed and recorded 7 Network Node Communications a Communicated between panels on single pair of copper wires or fiber optic cables b To enhance system surv...

Страница 3: ...ean control by event programming including as a minimum AND OR NOT and Timer functions 6 Control Panels Capability to accept firmware upgrades via connection with laptop computer without requirement o...

Страница 4: ...uding elevator recall elevator power shutdown door lock release door holder release HVAC unit shutdown smoke evacuation system activation and stair pressurization fan activation 5 Bill of Material OWN...

Страница 5: ...bmittals and shop drawings letter of certification from Gamewell FCI indicating proposed engineered system distributor is an authorized representative in good standing of the equipment supplied Includ...

Страница 6: ...of devices circuits zones and changes to system operation and custom label changes for devices or zones 4 System structure and software shall place no limit on type or extent of software modification...

Страница 7: ...ly Module PM 9 with batteries 3 80 Character LCD Display LCD E3 4 Intelligent Loop Main Board Interface ILI MB E3 or ILI95 MB E3 5 Optional Intelligent Loop Supplemental Interface ILI S E3 or ILI95 S...

Страница 8: ...or and control modules Display shall be liquid crystal type LCD clearly visible in dark and under all light conditions 3 Panel shall contain 4 functional keys a Alarm Acknowledge b Trouble Acknowledge...

Страница 9: ...cuits on SLC or NAC circuits disarrangement in system wiring failure of microprocessor or any identification module or system ground faults shall activate this trouble circuit Trouble signal shall be...

Страница 10: ...ull 4100 event history log supporting local and network functions If a main processor or network node is lost the entire log shall be accessible at any other Loop Interface board This shall be demonst...

Страница 11: ...e alarm systems in accordance with NFPA 72 as it is impossible to test all functions and verify items such as annunciation with only 1 person 24 Signaling Line Circuits Each ILI MB E3 module shall pro...

Страница 12: ...from 64 nodes to 122 nodes ANX SR Addressable Node Expander Single Ring will function in single 64 node systems 3 ANX shall provide a Ethernet Port for use in Systems Integration and for use with Eme...

Страница 13: ...e Detectors Provide 2 status LEDs Both LEDs shall flash under normal conditions indicating detector is operational and in regular communication with control panel and both LEDs shall be placed into st...

Страница 14: ...trol panel send data to panel representing analog level of products of combustion F Intelligent Multi Criteria Acclimating Detectors MCS ACCLIMATE2F 1 Addressable device designed to monitor a minimum...

Страница 15: ...1 The detector shall be comprised of four sensing elements including a photoelectric light scattering particulate sensor an electrochemical CO sensor a daylight filtered infrared IR sensor and solid...

Страница 16: ...hange over air handling systems to help prevent rapid distribution of toxic smoke and fire gases throughout areas served by duct system 3 Duct Smoke Detectors Mounted Above Ceiling or Otherwise Obstru...

Страница 17: ...D to blink latch on or latch off Flash under normal conditions indicating monitor module is operational and in regular communication with control panel P Addressable Dry Contact Monitor Modules MMI 10...

Страница 18: ...module NAC Wire for Style Z or Style Y Class A B with up to 1 amp of inductive signal or 2 amps of resistive signal operation Relay coil shall be magnetically latched to reduce wiring connection requi...

Страница 19: ...nel D NGA Network Graphic Annunciator 1 Main Menu a Configure allows Auto configuration of ILI MB S and NGA or ANX b Walk Drill enables Walk Test and Fire Drill function c I O Allows enable disable in...

Страница 20: ...arm system devices control panels and remote annunciators in finished areas Flush mount or surface mount fire detection and alarm system devices control panels and remote annunciators in unfinished ar...

Страница 21: ...anufacturer representative of Owner and fire department shall operate every installed device to verify proper operation and correct annunciation at control panel 3 Open signaling line circuits and not...

Отзывы: