Scope of Work/Materials
13850 (28 31 00) - 17
Bid No.041818-Installation of New Fire Alarm System at Adams Elementary School
2.
Mount in 4-inch (101.6-mm) square, 2-1/8-inch (54-mm) deep electrical box.
3.
IDC Zones: Suitable for Style B operation.
4.
LEDs: Flash under normal conditions, indicating monitor module is operational and in
regular communication with control panel.
P. Addressable Two Input and Two Output Modules (AMM-2RIF):
1.
Provide two isolated sets of Form-C contacts, which operate as a single pole double throw
switch. The module shall allow the control panel to switch these contacts on command.
The module shall not provide supervision for the notification appliance circuit (NAC).
Module shall have both normally open and normally closed connections available for field
wiring. Two input modules shall connect two supervised initiating device circuit (IDC) or
zone of conventional alarm initiating devices (any normally open dry contact device) to the
fire alarm control panel signaling line circuit (SLC) Loop.
2.
Mount in 4-inch (101.6-mm) square, 2-1/8-inch (54-mm) deep electrical box.
3.
IDC Zones: Suitable for Style B operation.
4.
LEDs: Four LEDs that are controlled by the panel to indicate status of each input and
output. Coded signals, transmitted from the panel, can cause the LED to blink, latch on, or
latch off. Flash under normal conditions, indicating monitor module is operational and in
regular communication with control panel.
P.
Addressable Dry Contact Monitor Modules (MMI-10F):
1.
Provide to connect 10 supervised Style B IDC zones or 5 supervised Style D IDC zones of
conventional alarm initiating devices (any N.O. dry contact device) to 1 of the fire alarm
control panel SLCs.
2.
Mount in factory-supplied MBB-2 or MBB-6 enclosure.
3.
LEDs: Flash under normal conditions, indicating monitor module is operational and in
regular communication with control panel.
M.
2-Wire Detector Monitor Modules (AMM-4SF):
1.
Provided to connect 1 supervised IDC zone of conventional 2-wire smoke detectors or
alarm initiating devices (any N.O. dry contact device).
2.
Mount in 4-inch (101.6-mm) square, 2-1/8-inch (54-mm) deep electrical box or to optional
surface-mounted back box.
3.
IDC Zone: Wired for Class A or B (Style D or Style B) operation.
4.
LEDs: Flash under normal conditions, indicating monitor module is operational and in
regular communication with control panel.
N.
2-Wire Detector Monitor Modules (MMI-6SF):
1.
Provided to connect 6 supervised Class B IDC zones of conventional 2-wire smoke
detectors or alarm initiating devices (any N.O. dry contact device).
2.
Mount in factory-supplied MBB-2 or MBB-6 enclosure.
3.
LEDs: Flash under normal conditions, indicating monitor module is operational and in
regular communication with control panel.
O.
Addressable Control Modules (AOM-2SF):