Scope of Work/Materials
13850 (28 31 00) - 16
Bid No.041818-Installation of New Fire Alarm System at Adams Elementary School
2. The sounder can be programmed to be silenced whenever a live page or active message
is being played over the system.
K.
Intelligent Aspiration Smoke Detector (AAD-8100):
1.
The AAD-8100 shall offer Very Early Warning Smoke Detection, Early Warning Smoke
Detection and Standard Smoke Detection settings.
2. It shall be tested and approved for coverage up to 8,000 sq. ft.
3. The ASD shall have dual source (blue LED and infra-red laser) optical smoke detection for
a wide range of fire detection with enhanced immunity to nuisance particulates.
4. The ASD shall operate in air flows from 0-4000 ft/min (0-1,219 m/min).
5. PipeIQ software shall provide pipe design, FAAST system configuration, and FAAST
system monitoring in a single software program.
6. The ASD shall allow 5 programmable alarm levels with time delays, including Alert, Action
1, Action 2, Fire 1, and Fire 2.
L. Intelligent Duct Smoke Detector Base (DNR, DNRW):
1.
In-Duct Smoke Detector Housing: Use ASD-PL2F intelligent photoelectric detector, ASD-
PL2FR intelligent remote test photoelectric detector or ASD-IL2F intelligent ionization
detector, which provides continuous analog monitoring and alarm verification from panel.
2.
When sufficient smoke is sensed, alarm signal is initiated, and appropriate action taken to
shut down or change over air handling systems to help prevent rapid distribution of toxic
smoke and fire gases throughout areas served by duct system.
3.
Duct Smoke Detectors Mounted Above Ceiling or Otherwise Obstructed from Normal
View: Provide an (
RTS151KEY)
Remote test station accessory, designed to test a remotely
located
Intelligent Duct Smoke detector
with remote alarm indicator.
4.
Each Detector: Install in either supply side or return side duct in accordance with local
mechanical code.
5. DST Sampling Tube
a. No tools needed for installation or removal
b. Installs/removes from front or back of detector
c. Available in 1 ft, 1.5ft, 3 ft, 5 ft, and 10 ft lengths
M.
Addressable Dry Contact Monitor Modules (AMM-2F):
1.
Provide to connect 1 supervised IDC zone of conventional alarm initiating devices (any
N.O. dry contact device) to 1 of the fire alarm control panel SLCs.
2.
Mount in standard deep electrical box.
3.
IDC Zone: Suitable for Style B operation.
N.
Addressable Dry Contact Monitor Modules (AMM-4F):
1.
Provide to connect 1 supervised IDC zone of conventional alarm initiating devices (any
N.O. dry contact device) to 1 of the fire alarm control panel SLCs.
2.
Mount in 4-inch (102-mm) square, 2-1/8-inch (54-mm) deep electrical box.
3.
IDC Zone: Suitable for Style D or Style B operation.
4.
LEDs: Flash under normal conditions, indicating monitor module is operational and in
regular communication with control panel.
O.
Addressable Dry Contact Monitor Modules (AMM-2IF):
1.
Provide to connect 2 supervised IDC zones of conventional alarm initiating devices (any
N.O. dry contact device) to 1 of the fire alarm control panel SLCs.